The Substation Section - ABB SAM600-IO Protocol Manual

Switchgear control unit
Hide thumbs Also See for SAM600-IO:
Table of Contents

Advertisement

Section 3
Substation Configuration description Language (SCL)
3.1
16
Substation
VoltageLevel
Bay
LNode
Communucation
Subnetwork
Connected AP
IED Name
IED Name
IED
Services
AccessPoint
Server
DataTypeTemplates
LNodeType
DO
DOType
DOType
DA
DAType
DAType
BDA
EnumType
IEC08000178 V1 EN-US
Figure 2:
IEC 61850: Principle structure of the SCL XML file
The arrows show the link between the different sections given when an IED is
integrated in the substation structure and/or in the communication structure. All
needed logical nodes of an IED are linked to the substation section by the SCL
tool.
A reference to GOOSE Control Blocks (GoCB) is included in the communication
section when GoCB is configured.

The substation section

The substation description in IEC 61850-6 clause 9 describes the arrangement of
the primary equipment. In addition, it also includes a list of the applied logical
nodes and the relation of those logical nodes to the primary equipment.
IED
LD
IED
LD
AccessPoint
Address
AccessPoint
Address
Authentication
LDevice
LN0
LN
DataSet
Report Control
GOOSE Control
Inputs
DOI
SettingControl
SDO
EnumType
Switchgear control unit SAM600-IO Version 2.2 IEC
1MRK 511 440-UEN A
LN
LN
GSE
GSE
DOI
DAI
IEC08000178.vsd
SEMOD129763-4 v4
Communication protocol manual