1MRK 511 440-UEN A
3.2
Switchgear control unit SAM600-IO Version 2.2 IEC
Communication protocol manual
Substation Configuration description Language (SCL)

The communication section

The organization of the physical IEDs to the communication network is
independent of the substation structure. The IEC 61850 standard defines the
communication network with no relation to an existing media or protocol. The
mapping to an existing media and protocol is specified in IEC 61850–8–1.
The IEC 61850 standard describes in part 7–2 the ACSI in a media and protocol
independent form. Part 8–1 specifies the mapping of this ACSI to the existing
MMS.
The communication section describes how information is routed between the IEDs
and contains the following parts:
Subnetworks
IEDs connected to different subnetworks
Access points per IED to subnetworks
Address
IP address of LAN network (is exceptionally part of the address elements)
Link to GoCB message in transmission direction (extended during signal
engineering and routing)
(client)
- Access Point (AP)
- Address
- GSE; GoCBs
Communication
Subnetwork
Communication
- Access Point (AP)
- Address
- GSE; GoCBs
IED
(server)
IEC06000101 V1 EN-US
Figure 3:
IEC 61850–6: Communication network
Additional information about the server is part of the IED.
IED
- Access Point (AP)
- Address
- GSE; GoCBs
Communication
AP
Communication
- Access Point (AP)
- Address
- GSE; GoCBs
IED
(server)
Section 3
IED
(client)
AP
Communication
- Access Point (AP)
- Address
- GSE; GoCBs
IED
(server)
en06000101.vsd
SEMOD129771-4 v3