Data
Input delay: 0 -> 1 or 1 -> 0 *)
Indication of the input signals
Input signal voltage:
-> 0 signal
-> Undefined signal
-> 1 signal
-> Residual ripple at 0 signal
-> Residual ripple at 1 signal
Input current per channel:
Input voltage +24 V
Input voltage +5 V
Input voltage +15 V
Maximum cable length:
-> Shielded
-> Unshielded
Protection against reversed voltage
Overvoltage protection
*) Input delay of the S500 module DO524. The transmission rate via serial buses has not been
taken into account.
2018/09/24
For further information, please refer to the existing documentation
System description Advant Controller 31.
3ADR010122, 8, en_US
Replacement devices: I/O modules > Replacement device 07DC92-AD
Value
Replacement device: Type. 8 ms
Existing device: Type. 7 ms
Replacement device: One yellow LED per
channel. The LED corresponds functionally to
the input signal.
Existing device: One green LED per channel.
The LED corresponds functionally to the input
signal.
24 V DC
Replacement device: -3 V...+5 V
Existing device: -6 V...+5 V
Replacement device: > +5 V...< +15 V
Existing device: > +5 V...< +13 V
Replacement device: +15 V...+30 V
Existing device: +13 V...+30 V
Replacement device: within -3 V...+5 V
Existing device: within -6 V...+5 V
Replacement device: within +15 V...+30 V
Existing device: within +13 V...+30 V
Replacement device: Type. 3.5 mA / 4 to
Existing device: Type. 7 mA / 4 to
Replacement device: > 0.5 mA
Existing device: ³ 0.2 mA
Replacement device: > 2 mA
Existing device: ³ 2 mA (at input voltage +13
V)
1000 m
600 m
Yes
Up to 30 V DC
AC31 Adapters