AC31 Adapters
Replacement devices: I/O modules > Replacement unit DC501-CS31-AD
1.5.6.2.2
Electrical connection
Fig. 87: Electrical connection
Table 81: Pin assignment CS31 bus (X1)
Connector / Terminal Pin
X1 / Shield
X1 / Shield
X1 / B2
X1 / B1
X1 / NC
X1 / Shield
140
1
2
3
4
5
6
Correction to existing documentation
In the existing documentation, connection X1 / 2 is incorrectly documented as
"free / not connected". On the replacement device DC501-CS31-AD, the selec-
tion of the pin assignment of connector X1 is identical to the realization of
device DC501-CS31. Thus, the pin assignment described in this document is
valid for the replacement device and the existing device.
3ADR010122, 8, en_US
Assignment / Signal
Shield (internally connected to pin 2 and 6. No internal
connection to functional earth)
Shield (internally connected to pin 1 and 6. No internal
connection to functional earth)
BUS 2
BUS 1
Not connected
Shield (internally connected to pin 1 and 2. No internal
connection to functional earth)
2018/09/24