ABB AC31 Assembly And Operation Manual page 21

Hide thumbs Also See for AC31:
Table of Contents

Advertisement

Planning/ com-
Software Automation Builder (see AC500 documentation):
missioning
07KT98-ARC-AD
07KT98-ARC-DP-AD
07KT98-ARC-ETH-AD
07KT98-ETH-DP-AD
07KT98-ARC-ETH-DP-AD
Software 907PC331
07KT94-ARC-AD
1.4.1.2.2
Functionality
Table 10: Existing device vs. replacement device
Designation
User program
User data
Digital inputs
Digital outputs
Digital inputs/outputs
Analog inputs
Analog inputs (can
also be configured as
digital inputs)
Analog outputs
2018/09/24
Replacement devices: CPU > Replacement device 07KT9x-AD
Existing device:
07KT98
1 MB
1 MB + 256 kB
RETAIN + 128 kB
(Flash EPROM)
24 in 3 groups (8
each), electrically iso-
lated
16 transistor outputs
in 2 groups (8 each),
electrically isolated
8 in 1 group, electri-
cally isolated
8 in 1 group, individu-
ally configurable to
0 ... 10 V, 0 ... 5 V,
±10 V, ±5 V, 0 ... 20
mA, 4 ... 20 mA,
Pt100 (2-wire or 3-
wire), differential
inputs, digital inputs
Yes
4 in 1 group, individu-
ally configurable to ±
10 V, 0 ... 20 mA, 4 ...
20 mA
3ADR010122, 8, en_US
Replacement device:
07KT9x-AD
CPU PM590: 2 MB
storage, memory card
slot
CPU PM590: 2 MB
storage, memory card
slot
16 in 2 groups (8
each). Caution: Poten-
tial reference/electrical
isolation
16 in 2 groups (8
each). Caution: Poten-
tial reference/electrical
isolation
16 in 2 groups (8
each). Caution: Poten-
tial reference/electrical
isolation
8 in 1 group, individu-
ally configurable 0..10
V, ±10 V, 0..20 mA,
4 ... 20 mA, Pt100/
PT1000/ Ni1000 (2-
wire or 3-wire), differ-
ential inputs, digital
inputs
Yes
4 in 1 group, individu-
ally configurable to ±
10 V, 0 ... 20 mA, 4 ...
20 mA
AC31 Adapters
Note
-
-
Potential reference/
electrical isolation has
changed *).
Potential reference/
electrical isolation has
changed *).
Potential reference/
electrical isolation has
changed *).
Potential reference
has changed *). Some
wiring adjustments
are required in part. 5
V measuring ranges
can be shown with 10
V measuring range.
Caution: AGND refer-
ence to ZP no longer
M
Caution: AGND refer-
ence to ZP no longer
M *). Some wiring
adjustments are
required in part.
21

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents