ABB AC31 Assembly And Operation Manual page 84

Hide thumbs Also See for AC31:
Table of Contents

Advertisement

AC31 Adapters
Replacement devices: I/O modules > Replacement device 07DC92-AD
Fig. 53: Process voltage connections - 07DC92-AD
Connector X4 also supplies the internal electronics for the device 07DC92-AD with 0.15 A.
1.5.2.8.2
Technical details of the I/O channels as binary inputs
Data
Connections
Input type according to EN 61131-2
84
NOTICE!
Process voltage must always be connected to connector X4 on device 07DC92-
AD.
Process voltage connections (X2, X3, X5, X6):
Maximum current for digital outputs X2 + X3: 4 A / 4 to
Maximum current for digital outputs X5 + X6: 4 A / 4 to
Input currents > 4 A require the connection of the second L+ contact of con-
nector X4.
For input currents > 8 A, additional L+ contacts from X2, X3, X5 or X6 must
be used.
The L+ contacts for the connectors X2, X3, X5 or X6 may be loaded with a
maximum of 4 A.
3ADR010122, 8, en_US
Value
X2 / 1.0 to 1.7
X3 / 2.0 to 2.7
X5 / 3.0 to 3.7
X6 / 4.0 to 4.7
Type 1 (realized through resistors)
2018/09/24

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents