AC31 Adapters
Replacement devices: CPU > Replacement device 07KT9x-AD
Digital inputs
Data
Number of channels per device
Connections
Division of channels in groups
Voltage supply
Common reference potential:
-> for group 1 (8 channels)
-> for group 2 (8 channels)
Electrical isolation:
Configurability of the inputs
Channels for high-speed counters
Indication of the input signals
Input signal voltage:
-> 0 signal
-> Undefined signal state
-> 1 signal
Input current per channel:
-> Input voltage = +24 V
-> Input voltage = + 5 V
-> Input voltage = +13 V
-> Input voltage = +30 V
Max. cable length unshielded
Max. cable length shielded
46
For further information, please refer to the existing documentation
System description Advant Controller 31.
3ADR010122, 8, en_US
Value
16
Connector X2 (terminals X5.0...X5.7)
Connector X3 (terminals X6.0...X6.7)
2 groups with 8 channels (not electrically iso-
lated!)
UP (supplies module DA501 and 502)
ZP (terminals 5.0 ... 5.07)
ZP (terminals 6.0 ... 6.07)
Electrical isolation from group to group is
no longer available.
Electrical isolation from DA501 and DA502
(reference ZP) to the rest of the device
(reference M) is available.
On DA501 and DA502, all channels have
the same potential ZP. Voltage supply
UP/ZP.
AGND1 and AGND2 of the analog chan-
nels are internally connected to ZP via
PTC resistorsFig. 18.
Input delay configurable (0.1 ms, 1 ms, 8 ms
and 32 ms). Default: 0.1 ms.
Ä Chapter 1.4.1.3.4.6 "Digital inputs/outputs"
on page 48
Channels for high-speed counters are imple-
mented with the inputs/outputs (channels: 4.0
and 4.1).
One yellow LED each per channel. The LED
corresponds functionally to the input signal.
24 V DC
-3 V...+5 V
+5 V ... + 15 V
+15 V ... + 30 V
Typ. 5.0 mA
> 1 mA
> 2 mA
< 8.0 mA
600 m
1000 m
2018/09/24