ABB AC31 Assembly And Operation Manual page 42

Hide thumbs Also See for AC31:
Table of Contents

Advertisement

AC31 Adapters
Replacement devices: CPU > Replacement device 07KT9x-AD
Output areas
No change to the wiring is necessary. The sensor is connected the same way as with the
±10 V / 0 ... 20
existing device 07KT98. Output load capability of voltage output: max. ±10 mA.
mA / 4 ... 20 mA
Fig. 34: Connection of output loads (voltage and current) to analog outputs
Battery and battery replacement
The AC31 adapters use another battery (lithium battery TA521).
For further information, please refer to the AC500 documentation.
Serial interface COM1
The serial interface COM1 is no longer available.
Programming can be performed via the serial interface COM2.
Serial interface
The serial interface DIAG is used for diagnosis and configuration. The DIAG interface is not
DIAG
electrically isolated and thus only intended for connection with the Automation Builder.
In the CPU or Automation Builder, the DIAG interface is accessed via the FBP interface. Conse-
quently, the information of the DIAG interface appears on the CPU display under the FBP inter-
face.
Connector / Pin
DIAG / 1
DIAG / 2
DIAG / 3
DIAG / 4
DIAG / 5
Serial interface COM2
Connector / Pin
COM2 / 1
COM2 / 2
COM2 / 3
42
Assignment / Signal
Not connected
TX
M
RX
FE
Assignment / Signal
FE
TX
RX
3ADR010122, 8, en_US