Special cases with rapidly flashing LEDs (approx. 5 Hz):
All 4 LEDs flash rapidly: An incorrect S500 module is connected to the device. The device
fails to initialize.
The LEDs of the CS31 bus, S-ERR bus and I/O bus flash rapidly: Invalid position of DIP
switches. The device fails to initialize.
The LEDs of the S-ERR bus and I/O bus flash rapidly: A checksum error occurred in an
internal Flash memory.
The LED of the I/O bus flashes rapidly: An error occurred in an internal RAM.
Table 47: LEDs of the S500 module DO524
LED
O0...O7 (see
No. 1 in the
following
figure)
I8 to I15 (see
No. 2 in the
following
figure)
O16 to O23
(see No. 3 in
the following
figure)
C24 to C31
(see No. 4 in
the following
figure)
Error indica-
tions right
(see No. 5 in
the following
figure)
Indication
supply
voltage (see
No. 6 in the
following
figure)
2018/09/24
Replacement devices: I/O modules > Replacement device 07DC92-AD
Status
Color LED off
Digital inputs/
Yellow Input/output is
outputs
Digital inputs/
Yellow Input/output is
outputs
Digital inputs/
Yellow Input/output is
outputs
Digital inputs/
Yellow Input/output is
outputs
Error indica-
Red
tion
Process
Green Process voltage
voltage
3ADR010122, 8, en_US
LED on
Input/output is acti-
not activated
vated (input voltage
is indicated even if
supply is switched
off)
Input/output is acti-
not activated
vated (input voltage
is indicated even if
supply is switched
off)
Input/output is acti-
not activated
vated (input voltage
is indicated even if
supply is switched
off)
Input/output is acti-
not activated
vated (input voltage
is indicated even if
supply is switched
off)
No error
Internal error
Process voltage OK -
not available
AC31 Adapters
LED flashes
-
-
-
-
Overload or
short circuit on
a channel of
the corre-
sponding
group