2.

7.2.12 Batt Loop Trip

Possible Causes
Measures
1.
2.
3.

7.2.13 Batt Off

Possible Causes
Measures
1.
2.
3.
4.
5.

7.2.14 Door Alarm

Possible Causes
Issue 10 (2017-08-08)
Check whether the load circuit breaker or fuse detection cable is disconnected. If so,
reconnect it.
The battery circuit breaker or fuse detection cable is loosely connected.
The battery circuit breaker has tripped or the battery fuse has blown.
The contactor is faulty.
Check whether the battery circuit breaker or fuse detection cable is loosely connected. If
so, reconnect the cable.
Check whether the battery circuit breaker has tripped or the battery fuse has blown. If so,
rectify the battery loop fault and then switch on the circuit breaker or replace the fuse.
Manually switch on or switch off the battery contactor and check whether the battery
current changes accordingly. If not, replace the contactor.
An AC power failure occurs.
Batteries are manually disconnected.
The battery disconnection voltage is set too high on the SMU.
Rectifiers are faulty.
The system configuration is not proper.
Check whether an AC power failure occurs. If yes, resume the AC power supply.
Check whether batteries are manually disconnected. If yes, confirm the reason of the
manual disconnection, and reconnect the batteries after the operation.
Check whether the battery disconnection voltage (43 V DC by default)is set too high on
the SMU. If yes, adjust it to a proper value.
Check whether the power system capacity is insufficient for the loads due to rectifier
failures. If yes, replace the faulty rectifier.
Check whether the load current is greater than the current power system capacity. If yes,
expand the power system capacity or reduce the load power.
This alarm is generated only for the power system that has door status sensor installed.
The cabinet doors are open.
The door status sensor is faulty.
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
7 Maintenance
48

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents