ETP4830-A1 Embedded Power
User Manual
6.4 Setting System Type
If the SMU01A is configured, set the system type based on the actual situation, as described
in
Table
type.
Table 6-3 Setting system type
Main Menu
Settings
6.5 Setting Battery Parameters
If battery parameters are incorrectly set, batteries will wear out earlier than necessary. Set the
parameters strictly according to requirements.
6.5.1 SMU01A
Set Qty of Battery to 1, set Rated Capacity to the total capacity of battery strings, and set
Charge Coef as required.
Table 6-4 Battery parameters for the SMU01A
Main Menu
Quick Settings
6.5.2 SMU01B and SMU01C
Set Battery String to 1, set Capacity to the total capacity of battery strings, and set Charge
Coef as required.
Issue 10 (2017-08-08)
6-3. If the SMU01B or SMU01C is configured, you do not need to reset the system
Second-Level
Menu
Site Summary
Second-Level
Menu
Qty of Battery
Rated Capacity
Charge Coef
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
Third-level
Default Value
Menu
System Type
Standard
Default Value
1
65 Ah
0.15 C10
6 Commissioning
Setting Value
ETP4830
Settings
1
Battery string
capacity
Range: 0.05
C10-0.25 C10
33