Connecting The Battery Supply - Huawei ETP4830-A1 User Manual

Embedded power
Hide thumbs Also See for ETP4830-A1:
Table of Contents

Advertisement

ETP4830-A1 Embedded Power
User Manual
Step 7 Set the SNMP trap destination address and trap port.
Step 8 Upload the MIB libraries HUAWEI-MIB.mib and HUAWEI-SITE-MONITOR-MIB.mib
to the NMS.
----End

6.10 Connecting the Battery Supply

Prerequisites
To avoid damage to batteries, reinstall the battery fuse only after correctly setting the battery
parameters for the monitoring unit.
Procedure
Step 1 Switch off the AC circuit breaker for the upper-level device, and then reinstall the battery
fuse.
Step 2 Switch on the AC circuit breaker for the upper-level device, and then reinstall the load fuses.
Step 3 Check whether the battery voltage and system output voltage are the same as the voltages
displayed on the SMU LCD. If not, ask the technical support personnel to rectify the fault.
Issue 10 (2017-08-08)
Figure 6-3 SNMPv3 parameters
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
6 Commissioning
41

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents