Maintenance

What this chapter contains

This chapter contains preventive maintenance instructions.

Safety

WARNING! Read the
performing any maintenance on the equipment. Ignoring the safety instructions can
cause injury or death.

Maintenance intervals

If installed in an appropriate environment, the drive requires very little maintenance.
This table lists the routine maintenance intervals recommended by ABB.
Capacitor reforming
Heatsink temperature
check and cleaning
Cooling fan change

Heatsink

The heatsink fins pick up dust from the cooling air. The drive runs into
overtemperature warnings and faults if the heatsink is not clean. In a normal
environment, the heatsink should be checked annually, in a dusty environment more
often.
Clean the heatsink as follows (when necessary):
1. Remove the cooling fan (see section
2. Blow clean compressed air (not humid) from bottom to top and simultaneously
use a vacuum cleaner at the air outlet to trap the dust. Note: If there is a risk of
the dust entering adjoining equipment, perform the cleaning in another room.
3. Replace the cooling fan.
Safety instructions
Maintenance
Every year of storage
Depends on the dustiness of the environment
(every 6 to 12 months)
Every 6 years if the ambient temperature does
not exceed 40 °C (104 °F).
Every 3 years if the ambient temperature is
higher than 40 °C (104 °F).
on the first pages of this manual before
Interval
Cooling
fan).
65
Instruction
See
Reforming the
capacitors.
See Heatsink.
See
Cooling
fan.