Table of contents 5 Table of contents 1 Introduction to the manual Contents of this chapter ................Applicability ..................Safety instructions ................Target audience ................... Categorization by frame size and option code ..........Use of component designations ..............Terms and abbreviations ................. Related documents ................
Page 6
Frames R1i…R4i ................Frame R6i ..................Frame R8i ..................Cabinet configuration overview ..............ACS880-204 configurations in Rittal VX25 enclosures ........ACS880-204 configurations in generic enclosures ........IGBT supply unit with frame R1i…R4i module ..........IGBT supply unit with frame R6i module ...........
Page 7
Table of contents 7 Kits for R8i module in 600 mm Rittal VX25 enclosure ........ Stage 1: Installation of common parts ..........Stage 2: Module installation parts ............Stage 3: BLCL AC busbars and quick connectors ........Stage 4: DC connection ..............Stage 5: Common mode filter busbars and DC connection flanges ....
Page 9
Replacing the fan of the LCL filter (BLCL-1x-x) ........... Replacing the fan of the LCL filter (BLCL-2x-x) ........... Replacing the cabinet cooling fans ............Cabinets with ABB air outlet kits ............Cabinets with other fan types ............IGBT supply module ................
Page 10
10 Table of contents Fuse bases for AC fuses (UL, CSA) ........... EMC/RFI filter ................Main contactors ................DC-side components ................. DC bus installation parts (for Rittal VX25 enclosures) ....... DC fuses ..................Fuse bases for DC fuses (IEC, UL, CSA) ..........Frame R6i ..................
Page 11
Table of contents 11 Main contactors ................Charging kits ................Varistor kit ACS880 for UL/CSA installations .......... AC connection of the LCL filter ............Busbars and quick connectors ............Quick connector ................DC-side components ................. DC bus installation parts (for Rittal VX25 enclosures) ....... DC busbars .................
Page 12
12 Table of contents Cable lugs ..................Typical power cable sizes ............... Electrical power network specification ............DC connection data ................Control unit connection data (ZCU/BCU) ............Efficiency ................... Protection classes ................Optical components ................Ambient conditions ................Materials ................... Auxiliary circuit current consumption ............
Introduction to the manual Contents of this chapter This chapter gives basic information on the manual. Applicability The manual is applicable to the ACS880-204 IGBT supply modules for user-defined cabinet installations. Safety instructions Follow all safety instructions delivered with the drive.
The module size can be identified from the basic code visible on the type designation label, for example, ACS880-204-0420A-3 where 0420A is the module size. The option codes of the module are listed after the plus sign.
Drive modules cabinet design and construction instructions 3AUA0000107668 BCU-02/12/22 control units hardware manual 3AUA0000113605 Supply module manuals ACS880-204 IGBT supply modules hardware manual 3AUA0000131525 ACS880 IGBT supply control program firmware manual 3AUA0000131562 ACS880 multidrives, Optimal grid control (option +N8053) supplement...
Page 18
Installation frames for ACS880 multidrive modules hardware manual 3AXD50000010531 Manuals and quick guides for I/O extension modules, fieldbus adapters, safety functions modules, etc. www.abb.com/drives/documents for all manuals on the Internet. You can find all documentation related to the multidrive modules on the Internet at...
Contents of this chapter This chapter describes how the IGBT supply unit works and also the hardware of the ACS880-204 IGBT supply module. Operation principle IGBT supply unit rectifies three-phase AC current to direct current for the intermediate DC link of the drive.
20 Operation principle and hardware description ■ Simplified main circuit diagram The following figure shows the simplified main circuit diagram of the rectifier. AC voltage AC fuses LCL filter IGBT supply module DC fuses DC voltage ■ Charging A charging circuit powers up the DC link capacitors of the drive system smoothly. Discharged capacitors cannot be directly connected to the full supply voltage.
Operation principle and hardware description 21 Overview diagram of the drive system The following figure shows a simplified diagram of a common DC bus drive system. AC supply Input AC fuses LCL filter IGBT supply unit Supply unit DC fuses DC bus Inverter DC fuses (with or without DC switch-disconnector) Inverter units (in the example, one of the two units consists of two inverter modules connected in parallel)
They also indicate if the components can be ordered from ABB or if the customer needs to acquire them separately. customer can order the components from ABB or if the customer needs to acquire them For components, see the ordering information.
The following figure shows a connection example of a supply unit with a frame size R6i module. module. AC supply network Cubicle Explanation Available through IGBT supply module cubicle Main switch-disconnector ABB or third party (ISU) AC supply network Charging switch-fuse ABB or third party IGBT supply Main switch-disconnector ABB or third party module cubicle...
The following figure shows a connection example of a supply unit with one frame R8i module. The following figure shows a connection example of a supply unit with one frame R8i module. AC supply network Incoming cubicle (ICU) Main switch-disconnector ABB or third party Cubicle Explanation Available through AC fuses ABB or third party...
(2×8i). modules (2×R8i). AC supply network Cubicle Explanation Available through Incoming cubicle (ICU) Main switch-disconnector ABB or third party AC supply network Incoming Main switch-disconnector ABB or third party AC fuses ABB or third party cubicle (ICU) AC fuses...
26 Operation principle and hardware description 28 Operation principle and hardware description IGBT supply module hardware Layout drawings The following figures show the layout of the IGBT supply modules and LCL filters. The following figures show the layout of the IGBT supply modules and LCL filters. ■...
Operation principle and hardware description 27 Operation principle and hardware description 29 ■ Frame R4i layout IGBT supply module (frames R3i and R4i) Frame R4i is pictured (frame R3i has a similar layout). Frame R4i is pictured (frame R3i has a similar layout). Item Explanation DC (output) connection (under connector cover)
30 Operation principle and hardware description 28 Operation principle and hardware description IGBT supply module (frame R6i) ■ Frame R6i layout Item Explanation Item Explanation DC connection AC connection DC (output) connection ZCU control unit (with slots for optional I/O modules) AC (input) connection I/O terminal blocks ZCU control unit (with slots for optional I/O...
Operation principle and hardware description 29 ■ Frame R8i hardware Frame R8i modules are used in single or parallel configurations. R8i modules run on wheels, and can easily be removed from the cubicle for cable installation or service. The quick connector at the back of the module couples when the module is inserted into the cubicle.
Page 30
30 Operation principle and hardware description This figure shows the layout of the R8i module. R8i module, front R8i module, back DC busbars Handle LEDs and fiber optic connectors Fan (standard speed-controlled fan shown; a direct-on-line fan is available as option +C188) Quick connector (three phases).
Operation principle and hardware description 31 ■ Connectors X50…X53 The cabinet builder must arrange an auxiliary voltage of 230 V AC (or 115 V AC with option +G304) to connector X50 to power the electronics of the power module. Also, the cabinet builder must arrange an auxiliary voltage of 230 V AC to connector X50 to power the main circuit interface board of the module during charging.
Page 32
32 Operation principle and hardware description Connectors X51, X52, X53 STO IN STO connectors of the mod- STO IN ule. Must be connected to 24 V DC for the module to start. 24V OUT 24 V DC for BCU and for 24V OUT STO IN to enable the mod- ule operation.
34 Operation principle and hardware description Operation principle and hardware description 35 Connectors X102 and X103 Connectors X102 and X103 WFU-xx module connector X102 Description WFU-xx module connector X102 Description Fan power supply, 24 V / 0 V Fan power supply, 24 V / 0 V WFU-xx module connector X103 Description WFU-xx module connector X103...
36 Operation principle and hardware description Connectors X50 and X1 ALCL-05-5 module connector X50 Description DOL fan L (230 V AC or option +G304: 115 V AC) DOL fan N (230 V AC or option +G304: 115 V AC) Temperature switch in Not in use Not in use Not in use...
38 Operation principle and hardware description Connectors X30 and X55 Connector X30 Description +C183: Heating element N (230 V AC or 115 V AC) +C183: Heating element L (230 V AC or 115 V AC) Not in use TP2, thermal cutoff circuit TP1, thermal cutoff circuit Not in use Not in use...
40 Operation principle and hardware description Connectors X30 and X55 Connector X30 Description +C183: Heating element N (230 V AC or 115 V AC) +C183: Heating element L (230 V AC or 115 V AC) Not in use TP2, thermal cutoff circuit TP1, thermal cutoff circuit Not in use +C188: DOL fan W...
Operation principle and hardware description 41 Control interfaces ■ Overview of control connections of ZCU-14 control unit It is possible to: • control the unit through the control panel and the fieldbus 26 Operation principle and hardware description • read the status information of the supply unit through the control panel, fieldbus and Overview of control connections of the control unit relay output.
42 Operation principle and hardware description ■ Overview of the control connections of the BCU control unit The diagram shows the control connections and interfaces of the BCU control unit. Analog and digital I/O extension modules and Control panel. fieldbus communication modules can be inserted into slots 1, 2 and 3.
Operation principle and hardware description 43 Supply unit control devices ■ Main disconnecting device You must equip the supply unit with a main disconnecting device. You can use either a main switch-disconnector [Q1.1] or a withdrawable main breaker [Q1]. With this switch, you can isolate the main circuit of the drive from the power line.
44 Operation principle and hardware description • view actual signals • change parameter settings • change between local and external control. To be able to start and stop the unit by the control panel, you must have the parameter-defined Run enable signal and Start enable signal on (1). The control panel must also be in local control mode.
Operation principle and hardware description 45 Type designation labels of the supply module and LCL filter module Each IGBT supply module and LCL filter module has a type designation label attached to it. The type designation stated on the label contains information on the specifications and configuration of the unit.
IGBT supply module Type designation describes the composition of the module in short. Note that in the type designation label of an IGBT supply module (ACS880-204), the type of the module is ACS880-104. The complete designation code is divided in subcodes: •...
Operation principle and hardware description 47 ■ LCL filter CODE DESCRIPTION Basic codes LCL filter for frames R1i…R4i IGBT supply modules. The delivery includes direct-on-line cooling fan as standard. ALCL LCL filter for frame R6i IGBT supply module. The delivery includes direct-on-line cooling fan as standard.
Moving and unpacking the module 49 Moving and unpacking the module Contents of this chapter This chapter gives basic information on moving, unpacking and lifting the modules. WARNING! Obey the safety instructions of the drive. If you ignore them, injury or death, or damage to the equipment can occur.
50 Moving and unpacking the module ■ Frames R6i…R8i The module is delivered on a wooden base, boxed in corrugated cardboard. The cardboard box is tied to the base with PET bands. 1. Cut off the bands. 2. Lift off the cardboard box. 3.
The installation must always be designed and made according to applicable local laws and regulations. ABB does not assume any liability whatsoever for any installation which breaches the local laws and/or other regulations. Furthermore, if the recommendations given by ABB are not followed, the drive may experience problems that the warranty does not cover.
52 Cabinet construction ■ Frame R6i The switching, disconnecting and protecting equipment can be placed inside the drive cabinet in the following way: 1. The AC supply coming to the drive cabinet is first connected to the main switch-disconnector [Q1] containing AC fuses. 2.
■ ACS880-204 configurations in Rittal VX25 enclosures The following figures show examples of ACS880-204 configurations that can be installed The following figures show examples of ACS880-204 configurations that can be installed in the Rittal TS 8 enclosure. in the Rittal VX25 enclosure.
ACS880-204 configurations in generic enclosures ACS880-204 configurations in generic enclosures The following figures show examples of ACS880-204 configurations that can be installed The following figures show examples of ACS880-204 configurations that can be installed in generic enclosure. in generic enclosure.
Cabinet construction 55 Cabinet construction 55 IGBT supply unit with frame R1i…R4i module ■ IGBT supply unit with frame R1i…R4i module The following figure shows an example of the R1i module in 400 mm wide Rittal TS 8 enclosure. The power cables are routed to the cabinet through the bottom. The following figure shows an example of the R1i module in 400 mm wide Rittal VX25 enclosure.
56 Cabinet construction IGBT supply unit with frame R6i module 56 Cabinet construction The following figure shows an example of the R6i module in 600 mm wide Rittal TS 8 enclosure. The power cables are routed to the cabinet through the bottom. ■...
Cabinet constructio IGBT supply unit with frame R8i module Cabinet construction 57 The following figure shows an example of the 1×R8i module in 600 mm wide Rittal TS enclosure. The customer must place the control equipment in a separate cabinet. ■...
58 Cabinet construction 58 Cabinet construction IGBT supply unit with frame 2×R8i modules ■ IGBT supply unit with frame 2×R8i modules The following figure shows an example of the 2×R8i modules in 1000 mm wide Rittal TS 8 enclosure. The customer must place the control equipment in a separate cabinet. The following figure shows an example of the 2×R8i modules in 1000 mm wide Rittal VX25 enclosure.
Cabinet construction 59 ■ Incoming cubicle Example of the AC fuse cooling The AC fuses must be cooled by forced cooling. If the fuses are not located in the same cubicle with the supply/rectifier module, the module cooling fan does not supply the cooling air for the fuses but you must use a separate cooling fan.
60 Cabinet construction Cabinet construction 61 RFI filter ■ RFI filter The following figure shows an example of installing RFI filter to the cabinet. For more The following figure shows an example of installing RFI filter to the cabinet. For more information about EMC requirements, see Electrical planning instructions for ACS880 information about EMC requirements, see Electrical planning instructions for ACS880 multidrive cabinets and modules (3AUA0000102324 [English]).
You can find the kit-specific assembly drawings, step-by-step instructions and kit information on the Internet. Go to https://sites-apps.abb.com/sites/lvacdrivesengineeringsupport/content. If needed, contact your local ABB representative. The example includes also cabinet assembly drawings that show each stage listed in the table. More detailed steps of each stage are described in the kit-specific assembly drawings.
Cabinet construction 65 ■ R6i module in a 600 mm wide Rittal VX25 enclosure Installation stages Installation stage Instruction code Kit code Kit ordering code Installation of common parts: Baying parts 3AXD50000336340 PE busbar [PE] 3AXD50000336104 Divider panel 3AXD50000336692 Common DC Flat-PLS assembly 3AXD50000333639 A-468-X-001- 3AXD50000333387...
Cabinet construction 75 ■ 1×R8i module in a 600 mm wide Rittal VX25 enclosure Installation stages Installation stage Instruction code Kit code Kit ordering code Installation of common parts: Baying parts 3AXD50000336340 PE busbar [PE] 3AXD50000336104 Divider panel 3AXD50000336692 Common AC Flat-PLS assembly 3AXD50000372782 A-468-X-011- 3AXD50000360772...
DC connection flanges 3AXD50000003403 A-468-8-232 3AXD50000003411 DC kit for fuses 3AXD50000025693 A-468-8-245 3AXD50000025659 1) This kit is not included in ABB’s standard design but may be used if you wish to have AC fuses on top of the LCL filter module.
Cabinet construction 87 ■ 2×R8i modules in a 1000 mm wide Rittal VX25 enclosure Installation stages Installation stage Instruction code Kit code Kit ordering code Installation of common parts: Baying parts 3AXD50000336340 PE busbar [PE] 3AXD50000336104 Divider panel 3AXD50000336692 Common AC Flat-PLS assembly 3AXD50000372782 A-468-X-011- 3AXD50000360772...
Cabinet construction 97 ■ 2×R8i modules in an 800 mm wide generic enclosure Parts to be installed Parts to be installed Instruction code Kit code Kit ordering code Module installation parts 3AXD50000013143 A-8-8-325 3AXD50000011158 Quick connectors 3AUA0000118667 A-468-8-100 3AUA0000119227 AC busbars 3AXD50000013187 A-8-8-144 3AXD50000011156...
Cabinet construction 99 ■ 3×R8i modules in a 1600 mm wide Rittal VX25 enclosure Installation stages Installation stage Instruction code Kit code Kit ordering code Installation of common parts: Baying parts 3AXD50000336340 PE busbar [PE] 3AXD50000336104 Divider panel 3AXD50000336692 Common AC Flat-PLS assembly 3AXD50000372782 A-468-X-011- 3AXD50000360772...
Cabinet construction 109 ■ 3×R8i modules in a 1400 mm wide generic enclosure Parts to be installed Parts to be installed Instruction code Kit code Kit ordering code Module installation parts A-6-8-326 3AXD50000011159 A-8-8-327 3AXD50000011160 Quick connectors 3AUA0000118667 A-468-8-100 3AUA0000119227 AC busbars A-X-8-145 3AXD50000011157...
The installation must always be designed and made according to applicable local laws and regulations. ABB does not assume any liability whatsoever for any installation which breaches the local laws and/or other regulations. Furthermore, if the recommendations given by ABB are not followed, the drive system may experience problems that the warranty does not cover.
112 Electrical installation Electrical safety precautions These electrical safety precautions are for all personnel who do work on the drive, motor cable or motor. WARNING! Obey these instructions. If you ignore them, injury or death, or damage to the equipment can occur. If you are not a qualified electrician, do not do installation or maintenance work.
The RFI filter is not suitable for use in IT (ungrounded) systems. Disconnect the filter before connecting the drive to the supply network. For instructions on how to do this, contact your local ABB representative. WARNING! If a drive with an RFI filter is installed on an IT system (an ungrounded power system), the system will be connected to earth potential through the filter capacitors of the drive.
114 Electrical installation Connecting the input power cables ■ Connection diagram (frames R1i…R4i) IGBT filter adapter filter supply module (1a) (1b) ISU cubicle (1b) (1a) Note: If the LCL filter is mounted onto the WBCA adapter, the LCL filter can be grounded through the fastening screws of the WBCA adapter (no additional grounding conductors are needed).
Electrical installation 115 ■ Connection diagram (frame R6i) LCL filter IGBT supply module (1a) Components for charging circuit (1b) ISU cubicle (1a) (1b) Note: Use a separate grounding PE cable (1a) or a cable with a separate PE conductor (1b) in addition if the conductivity of the shields does not meet the requirement for the PE conductor.
116 Electrical installation ■ Connection diagram (frame 1×R8i) LCL filter IGBT supply module (1a) Components for charging circuit (1b) ICU cubicle ISU cubicle (1b) (1a) Note: Use a separate grounding PE cable (1a) or a cable with a separate PE conductor (1b) in addition if the conductivity of the shields does not meet the requirement for the PE conductor.
Electrical installation 117 ■ Connection diagram (frame R8i multiples) IGBT supply modules LCL filter Components (1a) for charging circuit (1b) ISU cubicle ICU cubicle ISU cubicle (1b) (1a) Note: Use a separate grounding PE cable (1a) or a cable with a separate PE conductor (1b) in addition if the conductivity of the shields does not meet the requirement for the PE conductor.
118 Electrical installation ■ Connection procedure (frames R1i…R4i) Electrical installation 121 WARNING! Read the safety instructions given in Safety instructions for ACS880 Connection procedure (frames R1i…R4i) multidrive cabinets and modules (3AUA0000102301 [English]). If you ignore them, injury or death, or damage to the equipment can occur. WARNING! Repeat the steps described in section Electrical safety precautions...
Page 119
Electrical installation 119 Note: When the internal EMC filter is disconnected, the IGBT supply module is not EMC compatible. WARNING! If a supply module whose varistors are not disconnected is installed on an IT system (an ungrounded power system or a high resistance grounded [over 30 ohms] power system), the system is connected to earth potential through the varistors of the supply module.
Page 123
Electrical installation 123 Direct lug connection Screw lug detail Direct lug connection Instead of using the screw lugs included, the conductors of power 126 Electrical installation Instead of using the screw lugs included, the conduct- cables can be connected to the drive ors of power cables can be connected to the drive ter- terminals by removing the screw lugs and using crimp lugs.
124 Electrical installation ■ Connection procedure (frame R6i) WARNING! Read the safety instructions given in Safety instructions for ACS880 multidrive cabinets and modules (3AUA0000102301 [English]). If you ignore them, injury or death, or damage to the equipment can occur. 1. Stop the drive and do the steps in section Electrical safety precautions (page 112) before you start the work.
Electrical installation 125 Note that figure 2 is an example of a cable lead-through that has to be acquired by the customer. ■ Connection procedure (frame R8i) WARNING! Read the safety instructions given in Safety instructions for ACS880 multidrive cabinets and modules (3AUA0000102301 [English]). If you ignore them, injury or death, or damage to the equipment can occur.
Page 126
126 Electrical installation 2. Lead the cables into the inside of the cabinet. 360° grounding of the cable shield at the lead-through is recommended to suppress interference. 3. Twist the cable shields to bundles and connect to the cabinet PE (ground) busbar. Connect the separate ground conductors/cables to the cabinet PE (ground) busbar.
Page 127
Electrical installation 127 6. AC input of the LCL filter module BLCL-1x-x BLCL-2x-x BLCL-2x-x...
Page 128
Electrical installation 131 128 Electrical installation AC output of the LCL filter module 7. AC output of the LCL filter module BLCL-1x-x BLCL-2x-x...
For selecting a supply, see the auxiliary circuit current consumption in the technical data. WARNING! Use the LCL filter only with an ACS880-204 IGBT supply module. Use the filter only with an IGBT supply module of an appropriate frame size. WARNING!
Electrical installation 131 ■ Connecting the WBCA adapter to the LCL filter (frames R1i…R4i) Connect the cable (included) of the WBCA adapter to the L1/L2/L3 input terminals of the WFU-xx LCL filter module. Connect the power input to the L1/L2/L3/PE terminals of the WBCA adapter. Tightening torques: WFU-01: 1.7…1.8 N·m WFU-11, -21, -22: 15 N·m...
Electrical installation 133 ■ Internal circuit diagrams for LCL filters The following circuit diagrams show the internal connections of the LCL filter modules. WFU-01 and WFU-02...
IGBT supply modules of frames R1i…R4i are allowed to be used only with inverter modules that have charging circuit (eg, ABB inverter modules ACS880-104). The charging circuit data for each IGBT supply module (ACS880-204) and inverter module (ACS880-104) are shown in the following tables.
Installing the charging circuit (frames R6i and R8i) The cabinet builder must install and connect the charging circuit. For connections, see the example circuit diagrams. Consult ABB for more information on the components and wirings needed. Activate and tune the charging function in the control program. For information on tuning the parameters, see the firmware manual.
Electrical installation 141 Connecting the control cables ■ Default I/O connection diagrams 144 Electrical installation Control units of the drive. Connection procedure ■ Connection procedure Note: The instructions below are based on an example cabinet construction. They are Note: applicable to all possible solutions but only clarify the principles.
142 Electrical installation 6. Cut the cables to suitable length. Strip the cables and conductors. 7. Twist the cable shields into bundles and connect them to the ground terminal nearest to the terminal block. Keep the unshielded portion of the cables as short as possible. 8.
Page 143
Electrical installation 143 146 Electrical installation 146 Electrical installation The following figures show example fiber optic connections related to fan control. The following figures show example fiber optic connections related to fan control. The following figures show example fiber optic connections related to fan control. Direct-on-line cooling fan (option +C188) in IGBT supply module and LCL filter module Direct-on-line cooling fan (option +C188) in IGBT supply module and LCL filter module Direct-on-line cooling fan (option +C188) in IGBT supply module and LCL filter module...
144 Electrical installation Note: Connection between BINT board and BDFC board in the module is ready-made at the factory. Connecting a PC A PC (with eg, the Drive composer PC tool) can be connected as follows: 1. Connect an ACx-AP-x control panel to the unit either •...
Electrical installation 145 Installing optional modules WARNING! Obey the safety instructions of the drive. If you ignore them, injury or death, or damage to the equipment can occur. Note: Pay attention to the free space required by the cabling or terminals coming to the optional modules.
Installation checklist of the drive 147 Installation checklist of the drive Contents of this chapter This chapter contains a checklist of the mechanical and electrical installation of the drive. Checklist Examine the mechanical and electrical installation of the drive before start-up. Go through the checklist together with another person.
Page 148
148 Installation checklist of the drive Make sure that … The enclosures of the equipment in the cabinet have proper galvanic connection to the cabinet protective earth (ground) busbar; The connection surfaces at the fastening points are bare (unpainted) and the connections are tight, or separate grounding conductors have been installed.
Contents of this chapter This chapter instructs how to start up the IGBT supply unit. The instructions are valid for the example IGBT supply unit with ACS880-204 IGBT supply modules. The default device designations (if any) are given in square brackets, for example, main contactor [Q2].
150 Start-up Start-up procedure Tasks Safety WARNING! Follow the safety instructions during the start-up procedure. See Safety instructions for ACS880 multidrive cabinets and modules (3AUA0000102301 [English]). Only qualified electricians are allowed to start-up the drive. Checks/Settings with no voltage connected WARNING! Ensure that the disconnector of the supply transformer is locked to the off (0) position, that means no voltage is, or can not be, connected to drive inadvertently.
Page 151
Start-up 151 Tasks If time relays, or relays with delayed make contact or break contact are used in emergency stop circuits, check the relay time settings. See delivery-specific circuit diagrams and safety function specific docu- mentation (if applicable). Check the voltage settings of the auxiliary voltage transformers (if any) are according to the actual power line voltage.
Page 152
• Then select the correct supply unit type with parameter 195.31 Parallel connection rating id. • Reboot the control unit by parameter 196.08 Control board boot. • Check the correct voltage range, parameter 195.01 Supply voltage. • Reboot the control unit by parameter 196.08 Control board boot. ACS880-204-… Frame Parameter 195.31 selection 1130A-3 2×R8i...
Start-up 153 Tasks Drives with a charging switch [Q3]: Close the charging switch. Turn the operating switch [S21] to on (1) position to activate the Run enable signal and switch the main contactor [Q2] on. On-load checks Check that the supply module cooling fan rotates freely in the right direction. Validate the operation of safety functions (for example, emergency stop).
Contents of this chapter This chapter instructs how to maintain the IGBT supply module and how to interpret its fault indications. The information is valid for ACS880-204 IGBT supply modules and example cabinet installations of the modules. Note: The instructions do not cover all possible cabinet constructions.
Page 156
Cleaning IP22 and IP42 air inlet and outlet meshes Checking tightness of cable and busbar terminals. Tightening if needed. Checking ambient conditions (dustiness, corrosion, temperat- ure) Cleaning the heatsink of the sup- ply module ABB-SACE main circuit breaker maintenance Symbols...
Performance of on/off-site work (commissioning, tests, measurements or other work) Replacement Maintenance and component replacement intervals are based on the assumption that the equipment is operated within the specified ratings and ambient conditions. ABB recommends annual drive inspections to ensure the highest reliability and optimum performance. Note: Long term operation near the specified maximum ratings or ambient conditions may require shorter maintenance intervals for certain components.
158 Maintenance ■ Cleaning the door air inlets (IP22 and IP42) Check the dustiness of the air inlet meshes. If the dust cannot be removed by vacuum cleaning from outside through the grating holes with a small nozzle, proceed as follows: 1.
Maintenance 159 ■ Replacing the inlet door filters (IP54) 1. Stop the drive and do the steps in section Electrical safety precautions (page 112) before you start the work. 2. Remove the fasteners at the top of the grating. 3. Lift the grating and pull it away from the door. 4.
160 Maintenance Power connections ■ Retightening the power connections WARNING! Read the safety instructions given in Safety instructions for ACS880 multidrive cabinets and modules (3AUA0000102301 [English]). If you ignore them, injury or death, or damage to the equipment can occur. 1.
Reset the running time signal after fan replacement. Replacement fans are available from ABB. Do not use other than ABB specified spare parts. ■ Replacing the R1i and R2i module cooling fan...
162 Maintenance ■ Replacing the R3i and R4i module cooling fan WARNING! Read the safety instructions given in Safety instructions for ACS880 multidrive cabinets and modules (3AUA0000102301 [English]). If you ignore them, injury or death, or damage to the equipment can occur. 1.
Maintenance 163 ■ Replacing the R6i module cooling fan WARNING! Read the safety instructions given in Safety instructions for ACS880 multidrive cabinets and modules (3AUA0000102301 [English]). If you ignore them, injury or death, or damage to the equipment can occur. 1.
164 Maintenance ■ Replacing R8i module cooling fan (speed-controlled version) The module is equipped with a fan unit that contains two cooling fans. WARNING! Obey the safety instructions given in Safety instructions for ACS880 multidrive cabinets and modules (3AUA0000102301 [English]). If you ignore the safety instructions, injury or death, or damage to the equipment can occur.
Maintenance 165 ■ Replacing R8i module cooling fan (direct-on-line version) WARNING! Obey the safety instructions given in Safety instructions for ACS880 multidrive cabinets and modules (3AUA0000102301 [English]). If you ignore the safety instructions, injury or death, or damage to the equipment can occur.
Maintenance 167 ■ Replacing the circuit board compartment fan Frame R8i modules are equipped with a fan blowing air through the circuit board compartment. The fan is accessible from the front of the module. WARNING! Obey the safety instructions given in Safety instructions for ACS880 multidrive cabinets and modules (3AUA0000102301 [English]).
Page 168
168 Maintenance 8. Put the fan onto the threaded studs on the fan holder with the airflow direction arrow pointing towards the fan holder. 9. Install and tighten the four nuts removed earlier. 10. Connect the fan cable. 11. Align and push the fan holder into the module.
Page 169
Maintenance 169 12. Install and tighten the two M4×12 (T20) screws.
170 Maintenance ■ Replacing the fan of the LCL filter (filter for frames R1i…R4i) WARNING! Read the safety instructions given in Safety instructions for ACS880 multidrive cabinets and modules (3AUA0000102301 [English]). If you ignore them, injury or death, or damage to the equipment can occur. 1.
Maintenance 171 ■ Replacing the fan of the LCL filter (filter for frame R6i) Maintenance 175 WARNING! Replacing the fan of the LCL filter (filter for frame R6i) Read the safety instructions given in Safety instructions for ACS880 multidrive cabinets and modules (3AUA0000102301 [English]). If you WARNING! Only qualified electricians are allowed to carry out the work described below.
172 Maintenance ■ Replacing the fan of the LCL filter (BLCL-1x-x) WARNING! Read the safety instructions given in Safety instructions for ACS880 multidrive cabinets and modules (3AUA0000102301 [English]). If you ignore them, injury or death, or damage to the equipment can occur. 1.
Maintenance 173 ■ Replacing the fan of the LCL filter (BLCL-2x-x) WARNING! Read the safety instructions given in Safety instructions for ACS880 multidrive cabinets and modules (3AUA0000102301 [English]). If you ignore them, injury or death, or damage to the equipment can occur. 1.
174 Maintenance ■ Replacing the cabinet cooling fans Cabinets with ABB air outlet kits WARNING! Read the safety instructions given in Safety instructions for ACS880 multidrive cabinets and modules (3AUA0000102301 [English]). If you ignore them, injury or death, or damage to the equipment can occur.
Maintenance 175 IGBT supply module ■ Cleaning the heatsink The drive module heatsink fins pick up dust from the cooling air. The drive runs into overtemperature warnings and faults if the heatsink is not clean. When necessary, clean the heatsink as follows. WARNING! Read the safety instructions given in Safety instructions for ACS880 multidrive cabinets and modules (3AUA0000102301 [English]).
10. Unplug the signal connector cable (if any) in front of the module. 11. Pull the module out enough to attach a lifting chain to chain holes on top of the module. A lifting device for R6i module is available from ABB (order code: 3AXD50000196661, instruction code: 3AXD50000210268). Pull the module out.
Maintenance 179 ■ Replacing R8i module WARNING! Read the safety instructions given in Safety instructions for ACS880 multidrive cabinets and modules (3AUA0000102301 [English]). If you ignore them, injury or death, or damage to the equipment can occur. WARNING! • Do not use the module extraction/installation ramp with plinth heights which exceeds the maximum allowed height.
Page 180
180 Maintenance 4. Unplug the wiring on the front of the module. Unplug the connector (X50) at the top of the module. Move the wires aside. 5. Use a module pull out ramp or other lifting device to remove the module from the cabinet. If the ramp designed for Rittal enclosures is used, install it by placing the hooks of the ramp between the bottom plate and enclosure frame.
182 Maintenance LCL filter ■ Replacing the LCL filter (frame R6i) WARNING! Read the safety instructions given in Safety instructions for ACS880 multidrive cabinets and modules (3AUA0000102301 [English]). If you ignore them, injury or death, or damage to the equipment can occur. 1.
186 Maintenance ■ Replacing the LCL filter (frame R8i) WARNING! Read the safety instructions given in Safety instructions for ACS880 multidrive cabinets and modules (3AUA0000102301 [English]). If you ignore them, injury or death, or damage to the equipment can occur. WARNING! •...
Page 187
Maintenance 187 4. Unplug the signal connector cable on top of the LCL filter module. 5. Remove the five screws in the upper part of the LCL filter module. 6. Remove the four screws in the lower part of the LCL filter module. 7.
Capacitor failure is usually followed by damage to the unit and an input cable fuse failure, or a fault trip. Contact ABB if capacitor failure is suspected. Replacements are available from ABB. Do not use other than ABB specified spare parts. Contact an ABB service representative for spare parts and repair services.
190 Maintenance ■ Replacing the LCL filter capacitor (frames R3i and R4i) WARNING! Read the safety instructions given in Safety instructions for ACS880 multidrive cabinets and modules (3AUA0000102301 [English]). If you ignore them, injury or death, or damage to the equipment can occur. 1.
Maintenance 191 Control panel For detailed information on the control panel, see ACx-AP-x assistant control panels user’s manual (3AUA0000085685 [English]). ■ Cleaning the control panel Use a soft damp cloth to clean the control panel. Avoid harsh cleaners which could scratch the display window.
192 Maintenance ■ Replacing the BCU control unit battery Replace the real-time clock battery if the BATT OK LED is not illuminated when the control unit is powered. 1. Stop the drive and do the steps in section Electrical safety precautions (page 112) before you start the work.
Maintenance 193 Location Indication Control panel Continuous green The unit is functioning normally. Flickering green Data is transferred between the PC and the unit through the USB connection of the control panel. Blinking green There is an active warning in the unit. Continuous red There is an active fault in the unit.
2. If the control unit is powered from the faulty module, connect the control unit to another 24 V DC power supply. ABB strongly recommends using an external power supply with supply/rectifier units consisting of parallel-connected modules.
Note: • This chapter only lists the installation accessories available from ABB. All other parts must be sourced from a third party (such as Rittal) by the system integrator. For a listing, refer to the kit-specific installation instructions available at https://sites-apps.abb.com/sites/lvacdrivesengineeringsupport/content.
Page 196
196 Ordering information • L = liquid-cooled • w = cabinet width • 4 = 400 mm • 6 = 600 mm • 8 = 800 mm • s = module frame size / sizes • 1 = R1i • 2 = R2i •...
Contents size (see below for options) = 400 V (Range 380 … 415 V): • IGBT supply module with ZCU control unit (the module ACS880-204-008A0-3 ACS880-104-008A0-3+N2200 cooling fan has internal ACS880-204-0018A-3 ACS880-104-0018A-3+N2200 power supply) • ZMU memory unit with IGBT...
198 Ordering information ■ LCL filters LCL filter module has to be ordered separately. IGBT supply unit type Frame LCL filter size ACS880-204-... Type Ordering code Contents = 400 V (Range 380 … 415 V): • WFU-xx filter module 008A0-3...
Ordering information 199 114 Ordering information ■ Control panel Control panel The control panel is not included with the module but must be ordered separately. One The control panel is not included with the supply module but must be ordered separately. control panel is required for the commissioning of an ACS880 drive system, even if the Drive One control panel is required for the commissioning of an ACS880 drive system, even if composer PC tool is used.
200 Ordering information ■ Mechanical installation accessories and tools Air guide kits for LCL filter modules Air guide kits are used on top of the modules to guide cooling air. WFU filter air guides are designed to be used together with WFU filter and WBCA bottom connection adapter. LCL filter ACS880- Ordering code...
Ordering information 203 ■ AC-side components Main switch-disconnector kits You must equip the electric supply of a machinery with a main disconnecting device (IEC/EN60204-1). The main power line is equipped with a main switch-disconnector or a main circuit breaker [Q1]. This section lists suitable main switch-disconnectors. Frame size Main switch-disconnector Ordering code...
= 400 V (Range 380 … 415 V): 16 A, 690 V, 12 A, 600 V, Not available 008A0-3 170M1559D 3AUA0000115358 DFJ-12 class J from ABB gR, size 000 32 A, 690 V, 25 A, 600 V, Not available 0018A-3 170M1562D 10008131 DFJ-25...
= 400 V (Range 380 … 415 V): SCHAFFNER FN RFI filters are not available from 008A0-3 25 A (50 °C) 520 V AC 3120H-25-33 ABB. They must be acquired by the customer. SCHAFFNER FN 0018A-3 25 A (50 °C) 520 V AC For more specific information...
The main power line is equipped with main contactors [Q2]. Contactors are used for the on-off control of the main AC input power. Contactors are suitable for both IEC and UL/CSA installations. Main contactor (IEC, UL, CSA) ACS880-204-… Ordering code Type Data = 400 V (Range 380 …...
Ordering information 207 DC fuses DC fuses protect the module and drive DC bus against short circuits. ACS880-204-… Fuse (IEC, UL, CSA) Type Data Ordering code = 400 V (Range 380 … 415 V): 008A0-3 FWP-15A14F 15 A, 660 V...
208 Ordering information Fuse bases for DC fuses (IEC, UL, CSA) ACS880-204-… Fuse (IEC, UL, CSA) Type Data Ordering code = 400 V (Range 380 … 415 V): 008A0-3 US141 (Z331153F) 14 × 51 mm, 50 A, 690 V 3AUA0000089224...
(see below for options) = 400 V (Range 380 … 415 V): • IGBT supply module with ZCU control unit (the module ACS880-204-0210A-3 1×R6i ACS880-104-0250A-3+N2200 cooling fan has internal = 500 V (Range 380 … 500 V): power supply) ACS880-204-0210A-5 1×R6i...
Ordering information 211 114 Ordering information ■ Control panel Control panel The control panel is not included with the module but must be ordered separately. One The control panel is not included with the supply module but must be ordered separately. control panel is required for the commissioning of an ACS880 drive system, even if the Drive One control panel is required for the commissioning of an ACS880 drive system, even if composer PC tool is used.
A-6-6-355-VX Rittal VX25 Instruction code: 3AXD50000479849 Lifting device The lifting device is used for replacing converter modules in the ABB drives ACx enclosure and the Rittal VX25 enclosure. Used with … Ordering code Instruction code R6i; 600 mm Rittal VX25...
Ordering information 213 ■ AC-side components AC bus installation parts (for Rittal VX25 enclosures) The brackets in this kit act as a mounting base for the busbar supports of the Rittal Flat-PLS AC bus and ensure its correct placement and alignment inside the cabinet line-up. Note: The designs presented in this manual for Rittal VX25 enclosures employ the Rittal Flat-PLS busbar system.
214 Ordering information Main switch-disconnector kits You must equip the electric supply of a machinery with a main disconnecting device (IEC/EN60204-1). The main power line is equipped with a main switch-disconnector or a main circuit breaker [Q1]. This section lists suitable main switch-disconnectors. Frame size Main switch-disconnector (IEC) Ordering code...
RFI filter is used for improving the EMC characteristics of the unit and to fulfill category C2 requirements. See Electrical planning instructions for ACS880 multidrive cabinets and modules (3AUA0000102324 [English]). RFI filter ACS880-204-… Type Data Ordering code = 400 V (Range 380 … 415 V):...
216 Ordering information Switching and charging kit (mechanical parts) The switching and charging kit contains mechanical parts for installing switching and charging components into frame R6i IGBT supply module cubicle. Used with … Ordering code Kit code Illustration R6i; 600 mm 3AXD50000477494 A-6-6-405-VX Rittal VX25...
+ 4×INU) and 7 × IGBT supply unit DC capacitance (1×ISU + 6×INU). If the total DC link capacitance (including IGBT supply and inverter module DC capacitances) exceeds these limits, the components must be redimensioned. Contact ABB representative for more information. The capacitances of the IGBT supply module types and the inverter module types are specified in their technical data tables.
218 Ordering information Use double-insulated wire. For more detailed information on the charging components, see the technical data. Varistor kit ACS880 for UL/CSA installations The CVAR varistor board is used to protect the supply/rectifier module against excessive voltages peaks. The board shunts the current created by high voltage. The CVAR board must be attached into the cabinet and connected to the main circuit after the main contactor [Q2] and must have a PE connection as well.
Ordering information 219 Module and common mode filter busbars Instruction code: 3AUA0000115891 A common mode filter is needed with IGBT supply module. There is space for up to four toroidal cores. See the dimension drawings. Module and common mode filter busbars A common mode filter is needed with IGBT supply module.
220 Ordering information DC fuses DC fuses protect the module and drive DC bus against short circuits. Fuse (IEC, UL, CSA) ACS880-204-… Type Data Ordering code = 400 V (Range 380 … 415 V): Cooper-Bussmann 0210A-3 450 A, 690 V, size 1...
Page 222
222 Ordering information Ordering code format Option codes [Module type] +code [+code] … +C132: Marine type approval. For more information, see ACS880 +C132 marine type-approved drive modules and module packages For example, supplement (3AXD50000037752 [English]). ACS880-104-0470A-3 +E205 +C188 +C183: Heating element mounted to module base +C188: Direct-on-line cooling fan +E205: Internal du/dt filters (When the module is used as an IGBT supply module, it must always be ordered with +E205.)
LCL filter modules have to be ordered separately. IGBT supply Frame LCL filter unit type size Type Ordering code Contents ACS880-204-… = 400 V (Range 380 … 415 V): • +C183: Internal heat- ing element 0420A-3 1×R8i BLCL-13-5+C183+C188+G304 3AUA0000179948 • +C188: Direct-on-line 0580A-3 1×R8i...
Ordering information 225 ■ RFI filters RFI filter is used for improving the EMC characteristics of the unit and to fulfill category C2 requirements. See Electrical planning instructions for ACS880 multidrive cabinets and modules (3AUA0000102324 [English]). RFI filter Assembly kit for toroid ACS880- 204-...
226 Ordering information 114 Ordering information ■ Control panel Control panel The control panel is not included with the module but must be ordered separately. One The control panel is not included with the supply module but must be ordered separately. control panel is required for the commissioning of an ACS880 drive system, even if the Drive One control panel is required for the commissioning of an ACS880 drive system, even if composer PC tool is used.
Ordering information 227 ■ Control electronics Cabling of the electronics outside the module must be done by the customer. For the current consumption of the main components in the auxiliary circuit, see the technical data. Control unit You must equip each IGBT supply unit with one control unit (and memory unit). The delivery includes control unit.
228 Ordering information The following kits, each consisting of a pair of plastic fiber optic cables, are available from ABB: Length Kit type designation Ordering code NLWC-02 58988821 NLWC-03 58948233 NLWC-05 58948250 NLWC-07 58948268 10 m NLWC-10 58948276 Control circuit plug connectors The control circuit plug connector X50 is not included in the module kit and you must order it separately.
Ordering information 229 ■ Mechanical installation accessories and tools Module installation parts Module installation parts include, for example, top and bottom supports and air baffles for the supply and LCL filter modules. Used with … Ordering code Kit code Illustration 1×R8i;...
Page 230
230 Ordering information Used with … Ordering code Kit code Illustration 3×R8i; 800 mm 3AXD50000011160 A-8-8-327 generic Instruction code: 3AXD50000013813 2×R8i; 400 mm 3AXD50000360802 A-4-8-321-VX Rittal Instruction code: 3AXD50000349982 3×R8i; 600 mm 3AXD50000361700 A-6-8-322-VX Rittal Instruction code: 3AXD50000351930 3×R8i; 600 mm 3AXD50000011159 A-6-8-326 generic...
Ordering information 231 Used with … Ordering code Kit code Illustration 2×R8i; 800 mm 3AXD50000011158 A-8-8-325 generic Instruction code: 3AXD50000013143 Shrouds Shrouds are used for IP20 touch protection with the cabinet doors open. Used with … Ordering code Kit code Illustration 1 per R8i;...
232 Ordering information Ramp The ramp can be used when installing or removing an R8i module. Note: Do not use the ramp with plinth heights over 100 mm. The ramp is designed for a plinth height of 100 mm (the standard plinth height of Rittal VX25 enclosures). Used with …...
Ordering information 233 Main switch-disconnector kits You must equip the electric supply of a machinery with a main disconnecting device (IEC/EN60204-1). The main power line is equipped with a main switch-disconnector or a main circuit breaker [Q1]. This section lists suitable main switch-disconnectors. Note: For some of the IEC and UL high power units, you can use withdrawable main circuit breaker instead of the main switch-disconnector.
Page 234
234 Ordering information ACS880- Main switch-disconnector (UL, CSA) Ordering code 204-… Type Data 0310A-7 Switch kit OT-type UL 1200 U12 50 kA, 600 V, 1200 A 3AXD50000010814 0370A-7 Switch kit OT-type UL 1200 U12 50 kA, 600 V, 1200 A 3AXD50000010814 0540A-7 Switch kit OT-type UL 1200 U12...
In the table, these lower power units are marked with * in the first column. Note: UL-type air circuit breakers have IEC certification according to IEC 60947. See ABB SACE catalogs for further details. Main circuit breaker (IEC, 230 V) ACS880-204-…...
Page 236
236 Ordering information 1SDA073674R1 • YO E1.2..E6.2 220-240 Vac/dc 1SDA073687R1 • YC E1.2..E6.2 220-240 Vac/dc 1SDA073700R1 • YU E1.2..E6.2 220-240 Vac/dc 1SDA073725R1 • M E2.2..E6.2 220-250 Vac/dc 1SDA073781R1 • MOC E2.2..E6.2 1SDA073756R1 • AUX 6Q 400V E2.2..E6.2 1SDA073792R1 • KLC-S Key lock open N.20005 E2.2..E6.2 1SDA073807R1 •...
Page 237
Ordering information 237 Wagon (IEC, 230 V) ACS880-204-… Ordering code Type Data = 400 V (Range 380 … 415 V): E2.2-A_W_FP_2000HR- 1130A-3* 3-pole, rear hor. term., UL 3AXD50000048354 HR_UL E2.2-A_W_FP_2000HR- 1330A-3* 3-pole, rear hor. term., UL 3AXD50000048354 HR_UL E2.2-A_W_FP_2000HR- 1580A-3* 3-pole, rear hor.
Page 238
238 Ordering information Main circuit breaker (IEC, 115 V) ACS880-204-… Ordering code Type Data = 400 V (Range 380 … 415 V): 1130A-3* E2.2S-A 1200 1200 A, 690 V, 3P 3AXD50000048351 1330A-3* E2.2S-A 1600 1600 A, 690 V, 3P 3AXD50000048329 1580A-3* E2.2S-A 2000...
Page 239
Ordering information 239 Wagon (IEC, 115 V) ACS880-204-… Ordering code Type Data = 400 V (Range 380 … 415 V): E2.2-A_W_FP_2000HR- 1130A-3* 3-pole, rear hor. term., UL 3AXD50000048354 HR_UL E2.2-A_W_FP_2000HR- 1330A-3* 3-pole, rear hor. term., UL 3AXD50000048354 HR_UL E2.2-A_W_FP_2000HR- 1580A-3* 3-pole, rear hor.
Page 240
240 Ordering information Main circuit breaker (UL, CSA: 230 V) ACS880-204-… Ordering code Type Data = 400 V (Range 380 … 415 V): 1130A-3 E2.2S-A 1200 1200 A, 600 V, 65 kA, UL 3AXD50000048328 1330A-3 E2.2S-A 1600 1600 A, 600 V, 65 kA, UL...
Page 241
Ordering information 241 Main circuit breaker (UL, CSA: 115 V) ACS880-204-… Ordering code Type Data = 400 V (Range 380 … 415 V): 1130A-3 E2.2S-A 1200 1200 A, 600 V, 65 kA, UL 3AXD50000048351 1330A-3 E2.2S-A 1600 1600 A, 600 V, 65 kA, UL...
Page 242
242 Ordering information Wagon (UL, CSA) ACS880-204-… Ordering code Type Data = 400 V (Range 380 … 415 V): E2.2-A_W_FP_2000HR- 1130A-3 3-pole, rear hor. term., UL 3AXD50000048354 HR_UL E2.2-A_W_FP_2000HR- 1330A-3 3-pole, rear hor. term., UL 3AXD50000048354 HR_UL E2.2-A_W_FP_2000HR- 1580A-3 3-pole, rear hor. term., UL...
Ordering information 243 IEC bus bar shim kit The following shim kits are available for adapting E2.2S-A, E4.2S-A and E6.2V-A air circuit breakers to IEC bus bars. Type Data Ordering code Illustration EMAX2 E2.2 bus bar E2.2S-A 3AXD50000286324 shim kit Instruction code: 3AXD50000286072 EMAX2 E4.2 bus bar...
The AC fuses protect the input cables, main contactor [Q2] and the module against short circuits. Main AC fuses are used only with the main contactor [Q2] solution. Module-specific AC fuses are used with the main circuit breaker [Q1] solution. Fuse (IEC) ACS880-204-… Frame size Ordering code Type Data = 400 V (Range 380 …...
Page 245
Ordering information 245 Fuse (UL, CSA) ACS880-204-… Frame size Ordering code Type Data = 690 V (Range 525 … 690 V): 0310A-7 1×R8i 170M6408 500 A, 690 V 3AUA0000136232 0370A-7 1×R8i 170M6410 630 A, 690 V 68335418 0540A-7 1×R8i 170M6413...
246 Ordering information AC fuses in IGBT supply module cubicle or LCL filter cubicle When using main circuit breaker, the AC fuses protect the modules against short circuits. Fuse (IEC) ACS880-204-… Frame size Ordering code Type Data = 400 V (Range 380 … 415 V): 1130A-3 2×R8i...
See also Main switch-disconnector kits (page 233) Main circuit breakers and wagons (page 235). Main contactor (IEC) ACS880-204-… Ordering code Type Data = 400 V (Range 380 … 415 V): 800 A(I ), 1000 V (U...
Page 248
248 Ordering information Main contactor (IEC) ACS880-204-… Ordering code Type Data 2050 A (I ), 1000 V (U 1570A-7 AF2050-30-22-70 3AUA0000051805 100 … 250 V/50 … 60 Hz Main contactor (UL/CSA) ACS880-204-… Ordering code Type Data = 400 V (Range 380 … 415 V):...
+ 4×INU) and 7 × IGBT supply unit DC capacitance (1×ISU + 6×INU). If the total DC link capacitance (including IGBT supply and inverter module DC capacitances) exceeds these limits, the components must be redimensioned. Contact ABB representative for more information. The capacitances of the IGBT supply module types and the inverter module types are specified in their technical data tables.
OHB65J6 or OHB45J6 with ON/OFF indication, see also content of OS_P switches. Minimum recommended wire sizes for the charging kits: • Consult ABB. Use double-insulated wire. For more detailed information on the charging components, see the technical data. Varistor kit ACS880 for UL/CSA installations The CVAR varistor board is used to protect the supply/rectifier module against excessive voltages peaks.
Instruction code: 3AXD50000002577 3AXD50000416509 Note: This kit is not included 1 per in ABB’s standard BLCL-1x-x; Rittal A-6-8-110-VX design but may be module used if you wish to have AC fuses on top of the LCL filter mod- ule.
Page 253
Ordering information 253 Used with … Ordering code Kit code Illustration 1 per BLCL-2x-x; Rittal 3AXD50000360796 A-4-8-107-VX module Instruction code: 3AXD50000353491 1 per BLCL-2x-x; generic 3AXD50000011155 A-468-8-109 module Instruction code: 3AXD50000013246 1 per BLCL-2x-x; 3×R8i 3AXD50000371143 A-6-8-108-VX Rittal module Instruction code: 3AXD50000352999...
254 Ordering information Busbars and quick connectors The power input of the supply module is connected to the module through a quick connector. Used with … Ordering code Kit code Illustration 1×R8i; 600 mm 3AXD50000416493 A-6-8-130-VX Rittal Instruction code: 3AXD50000384945 1×R8i;...
Ordering information 255 Used with … Ordering code Kit code Illustration 3×R8i; 1600 mm 3AXD50000371129 A-X-8-143-VX Rittal Instruction code: 3AXD50000360444 3×R8i; 1400 mm 3AXD50000011157 A-X-8-145 generic Instruction code: 3AXD50000013810 Quick connector Used with Ordering codes Kit code Illustration 1 per All enclosure types 3AUA0000119227 A-468-8-100...
256 Ordering information ■ DC-side components DC bus installation parts (for Rittal VX25 enclosures) The brackets in this kit act as a mounting base for the busbar supports of the Rittal Flat-PLS DC bus and ensure its correct placement and alignment inside the cabinet line-up. Note: The designs presented in this manual for Rittal VX25 enclosures employ the Rittal Flat-PLS busbar system.
Ordering information 257 Used with … Ordering code Kit code Illustration R8i; All enclosures 3AXD50000003411 A-468-8-232 Instruction code: 3AXD50000003403 Module and common mode filter busbars A common mode filter is needed with each IGBT supply module. There is space for up to four toroidal cores.
258 Ordering information DC fuses DC fuses protect the module and drive DC bus against short circuits. ACS880-204-… Fuse (IEC, UL, CSA) Ordering code 2nd type fuse Type Data = 400 V (Range 380 … 415 V): 0420A-3 Cooper-Bussmann 900 A, 690 V,...
Page 259
Ordering information 259 ACS880-204-… Fuse (IEC, UL, CSA) Ordering code 2nd type fuse Type Data 0370A-7 Cooper-Bussmann 800 A, 1250 V, 63919128 size 3 170M6546 0540A-7 Cooper-Bussmann 1100 A, 1000 V, 68736021 size 3 170M6549 0720A-7 Cooper-Bussmann 800 A, 1250 V,...
Ordering information 263 ■ Air outlet kits Air outlet kits 400 mm cabinet Used with … Ordering code Kit code Illustration IP20 (IEC) 3AUA0000125203 A-4-X-042 Instruction code: 3AXD50000001983 IP20 (IEC) 3AUA0000125201 A-4-X-062 Instruction code: 3AXD50000001982 Note: Fan to be ordered separ- ately IP42 (IEC) 3AUA0000114968...
264 Ordering information Used with … Ordering code Kit code Illustration IP54 (IEC) 3AXD50000009187 A-4-X-064 Instruction code: 3AXD50000010001 Note: Fan to be ordered separ- ately IP54 (UL) 3AXD50000010362 A-4-X-067 Instruction code: 3AXD50000010284 Note: Fan to be ordered separ- ately Air outlet kits 600 mm cabinet Used with …...
Ordering information 265 Used with … Ordering code Kit code Illustration IP54 (IEC) 3AXD50000009189 A-6-X-065 Instruction code: 3AXD50000010004 Note: Fan to be ordered separ- ately IP54 (UL) 3AXD50000010327 A-6-X-066 Instruction code: 3AXD50000010004 Note: Fan to be ordered separ- ately Air outlet kits 800 mm cabinet Used with …...
Page 266
266 Ordering information Used with … Ordering code Kit code Illustration IP54 (IEC) 3AXD50000009187 A-4-X-064 Instruction code: 3AXD50000010001 Note: Fan to be ordered separ- ately IP54 (UL) 3AXD50000010362 A-4-X-067 Instruction code: 3AXD50000010284 Note: Fan to be ordered separ- ately...
268 Ordering information • Relpol PI84-24DC-M41G relay • Rated load (capacity): 8 A / 24 V DC • Rated power consumption: 0.4 … 0.48 W DC • GZT80 relay socket • 600 mm of AWG24, 300 V, UL1569 (or equivalent material, valid for PVC insulation only) wire •...
272 Technical data Ratings Light-overload Capa- No-overload use Heavy-duty use citance ACS880- Frame 204-… A (DC) A (AC) A (DC) A (DC) A (DC) (DC) (DC) = 400 V (with U = 3~400 V AC and U = 566 V DC) input output 008A0-3...
274 Technical data ■ Derating Ambient temperature derating In the temperature range +40…50 °C (+104…122 °F), the rated output current is derated by 1 percentage point for every added 1 °C (1.8 °F). The output current can be calculated by multiplying the current given in the rating table by the derating factor (k): 1.00 0.90 0.80...
Derating factor 0.80 For a more accurate derating, use the DriveSize PC tool. Type equivalence table Cabinet-installed type IGBT supply unit type Basic module type Frame ACS880-207-… ACS880-204-… ACS880-104… = 400 V (Range 380 … 415 V) 008A0-3 ACS880-104-008A0-3 1×R1i 0018A-3 ACS880-104-0018A-3 1×R2i...
3080A-7 ACS880-104-0600A-7 6×R8i Cabinet-installed units available from ABB IGBT supply unit types available from ABB as modules IGBT supply modules used. The quantity of the modules is shown in the Frame column. Fuses For fuse types, see the ordering information.
Page 277
Technical data 277 Charging fuses Charging contactor Charging kit code Type Rating Info Type Rating 3AXD50000002846 OFAA000GG50 50 A, 690 V, HRC fuse AF96-30-22- 100 … 250 V AC/DC, 50/60 Hz IEC 000 link 3AXD50000015666 OFAA000GG16 16 A, 690 V, HRC fuse AF96-30-22- 100 …...
Page 278
278 Technical data Charging fuses Charging contactor Charging kit code Type Rating Info Type Rating 3AXD50000022525 OFAA000GG40 40 A, 690 V, HRC fuse AF52-30-22- 100 … 250 V AC/DC, 50/60 Hz IEC 000 link 3AXD50000022529 OFAA000GG35 35 A, 690 V, HRC fuse AF52-30-22- 100 …...
Technical data 279 Charging kit code Charging switch Charging resistor Type Rating Type Rating 3AXD50000022535 OS160GD04F 160 A, 690 V, 50 kA, 4-pole CBH 215 C H 414 5R0 5 ohm 3AXD50000025574 OS160GD04F 160 A, 690 V, 50 kA, 4-pole CBH 215 C H 414 5R0 5 ohm 3AXD50000025575...
Page 280
280 Technical data Charging fuses Charging contactor Charging kit code Type Rating Info Type Rating 3AXD50000017083 LPJ-200SP 200 A, 600 V AC Class J AF205-30-22 100 … 250 V AC/DC, 50/60 Hz 3AXD50000017084 LPJ-100SP 100 A, 600 V AC Class J AF305-30-11 100 …...
Technical data 285 Above Front Left Right ACS880-204-… 3080A-7 Definitions Above Free space to enable cooling air flow Front Free space for cabling Left Free space for smooth installation Right Free space for smooth installation Allowable mounting orientations The modules must be mounted upright unless other orientations are expressly allowed below.
Technical data 287 ACS880-204-… Air flow for IGBT supply mod- Noise lossISU lossLCL /min 3080A-7 60.9 33.0 12300 7240 Definitions Heat dissipation. Total losses of the ISU module at nominal power lossISU Heat dissipation. Total losses of the LCL filter module at nominal power...
Technical data 289 Typical power cable sizes The tables below give current carrying capacity (I ) for aluminum and copper PVC/XLPE Lmax insulated cables. A correction factor K = 0.70 is used. Time const is the temperature time constant of the cable. The cable sizing is based on max.
Page 290
290 Technical data Copper cable PVC insulation XLPE insulation Conductor temperature 70° Conductor temperature 90° Size ⌀ [mm] Time const. [s] Time const. [s] Lmax Lmax 3 × 1.5 + 1.5 3 × 2.5 + 2.5 (3 × 4 + 4) 3 ×...
*) Type gG according to IEC 60269 Maximum allowed operating time is <0.1 s for fuses mentioned above. For supply units with R8i module(s): Supply units with the ABB-defined main switch-disconnector and fuses: • Rated peak withstand current I = 105 kA •...
ACS880-204-xxxxA-5: 513…675 V DC. This is indicated in the type designation label as typical output voltage levels 540/648/675 V DC ACS880-204-xxxxA-7: 709…932 V DC (709…810 V DC for UL/CSA). This is indic- ated in the type designation label as typical output voltage levels 709/810/932 V DC (810 V DC for UL/CSA).
Maximum long-term tensile load: 1 N • Flexing: Max. 1000 cycles ABB drive products in general utilize 5 and 10 MBd (megabaud) optical components from Avago Technologies’ Versatile Link range. Note that the optical component type is not directly related to the actual communication speed.
58 … 150 Hz 1 g Classification of environ- IEC 60068-2-6:2007, tion of environmental con- mental conditions - Part 3: Tested in ABB multidrive EN 60068-2-6:2008 Envir- ditions - Part 3: Classifica- Classification of groups of cabinet (ACS880-x07) ac- onmental testing Part 2-6:...
IEC 62635 guidelines. To aid recycling, plastic parts are marked with an appropriate identification code. Contact your local ABB distributor for further information on environmental aspects and recycling instructions for professional recyclers. End of life treatment must follow international and local regulations.
296 Technical data Type cont start cont LCL filter module (ALCL-05-5) fan (+C188) 230 V AC 0.23 0.37 • Options +A013+C188+G304 230 V AC 0.29 0.37 115 V AC 0.59 LCL filter module (BLCL-1x-x) fan (+C188) 230 V AC 0.68 1.25 •...
Control units of the drive 299 Control units of the drive Contents of this chapter This chapter • describes the connections of the control unit, • contains the specifications of the inputs and outputs of the control unit. General The ZCU-14 control unit is used with IGBT supply module frame sizes R1i…R4i and R6i. The ZCU units consists of a ZCON control board contained in a plastic housing.
300 Control units of the drive 146 Supply control unit Layout and connections ZCU-14 layout and connections The layout and connections of the ZCU-14 are shown below. The layout and connections of the ZCU-14 are shown below. Description Description XPOW External power input XPOW External power input X202...
Control units of the drive 301 BCU-x2 control unit layout and connections Description I/O terminals (see following diagram) SLOT 1 I/O extension, encoder interface or fieldbus adapter module connection. (This is the sole location for an FDPI-02 diagnostics and panel interface.) SLOT 2 I/O extension, encoder interface or fieldbus adapter module connection...
Page 302
302 Control units of the drive Description Analog inputs Analog outputs Digital inputs, Digital input interlock (DIIL) XRO3 XD24 XPOW XDIO Digital input/outputs XD2D Drive-to-drive link XRO2 XDIO XD24 +24 V output (for digital inputs) XETH Ethernet port – Not in use XRO1 XPOW External power input...
Control units of the drive 303 Default I/O diagram of the supply control unit The diagram below shows the default I/O connections on the supply control unit (A51), and describes the use of the connections in the supply unit. The wire size accepted by all screw terminals (for both stranded and solid wire) is 0.5 … 2.5 mm (24…12 AWG).
(nominal impedance 100 to 165 ohm, for example Belden 9842) for the wiring. For best immunity, ABB recommends high quality cable. Keep the cable as short as possible. Avoid unnecessary loops and parallel runs near power cables such as motor cables.
The BCU-x2 has an on-board data logger that collects real-time data from the power modules to help fault tracing and analysis. The data is stored onto the SDHC memory card inserted into the SD CARD slot and can be analyzed by ABB service personnel.
wer supply Connector pitch 5 mm, wire size 2.5 mm 24 V (±10%) DC, 2 A 306 Control units of the drive External power input. Two supplies can be connected for redundancy. ay outputs RO1…RO3 Connector data Connector pitch 5 mm, wire size 2.5 mm O1…XRO3) 250 V AC / 30 V DC, 2 A Power supply (XPOW)
Page 307
Control units of the drive 307 Analog inputs AI1 and AI2 Connector pitch 5 mm, wire size 2.5 mm (XAI:4 … XAI:7). Current input: –20…20 mA, R = 100 ohm Current/voltage input mode selection by Voltage input: –10…10 V, R >...
308 Control units of the drive Control units of the drive 137 ■ BCU-x2 ground isolation diagram Ground isolation diagram XPOW +24VI +24VI +VREF -VREF AGND AI1+ Common mode voltage AI1- AI2+ between each AI input and AI2- AGND is +30 V AGND AGND XD2D...
Control units of the drive 309 Supply control unit 155 ■ ZCU-1x ground isolation diagram Ground isolation diagram (ZCU) XPOW +24VI +VREF -VREF AGND AI1+ Common mode voltage between AI1- channels ±30 V AI2+ AI2- AGND AGND XD2D BGND XRO1, XRO2, XRO3 XD24 DIIL +24VD...
Dimension drawings 311 Dimension drawings Contents of this chapter This chapter shows dimensions of the ACS880-204 IGBT supply modules and accessories.
Dimension drawings 345 Charging switches ■ OS30FAJ22F OA 3G01 OSZ 4 OA 1G10 OA4B1C max 3+3 max 1+1 75...80 Test 35,6 27,6 30,8 14,3 EN 50022 14...85 Ø66 135...210 Dimensions in mm 1 mm = 0.0394 in...
348 Dimension drawings ■ OS160GD04F 138...205 (OXP 6x161) 33,4 53,3 95,5 8,5 7,2 17,5 114,5 Back connection types: Ø9 >14 17,5 OS160GD04F 181.5 mm 130 mm 100 mm 160 mm 175 mm 190 mm Dimensions in mm 1 mm = 0.0394 in...
Dimension drawings 363 Air circuit breakers ■ E2.2S-A (UL/CSA/IEC) Horizontal terminals 1600 A … 2000 A Moving part Vertical terminals 1600 A … 2000 A Fixed part Tightening torque 8.6 Nm - 76 lb in Segregation Door position Connected, test, disconnected distances Grounding Roof insulation or insulated material Mounting fixed part screws...
364 Dimension drawings ■ E4.2S (IEC) Horizontal terminals 3200 A Door position Vertical terminals 3200 A Earthing device Horizontal terminals 4000 A Mobile part Vertical terminals 4000 A Fixed part Tightening torque 3200 A 20 Nm Segregation (where envisaged) Tightening torque 4000 A 20 Nm Distance from connected for testing to isolated...
Dimension drawings 365 ■ E4.2S-A (UL/CSA/IEC) Horizontal terminals 2500 A Moving part Vertical terminals 2500 A Fixed part Tightening torque 20 Nm - 177 lb in Segregation Door position Connected, test, disconnected distances Grounding Roof insulation or insulated material Mounting fixed part screws...
366 Dimension drawings ■ E6.2V-A (UL/CSA/IEC) Horizontal terminals 5000 A Moving part Vertical terminals 5000 A Fixed part Tightening torque 20 Nm - 177 lb in Segregation Door position Roof insulation or insulated material Mounting fixed part screws M8×25 provided Tightening torque 20 Nm - 177 lb in...
156 Dimension drawings Dimension drawings 367 ZCU-14_dimensions.pdf ZCU-14 control unit ZCU control unit 44.7 54.5 Dimensions in mm 1 mm = 0.0394 in...
ACX-AP-x_dimensions control panel with door mount kit.pdf Dimension drawings 155 370 Dimension drawings ACX-AP-x control panel with door mounting kit ACS-AP-x control panel with DPMP-01 door mounting kit 81.0 [3.19] 86.5 [3.41] 123.1 [4.85] 125.0 [4.92] Cutting in the cabinet door: 109 mm × 223 mm (4.29 in × 8.78 in) Plate thickness: 1.5 …...
• understanding the internal connections and operation of the cabinet-installed drive with an IGBT supply unit, and • learning how to wire an (ACS880-204) IGBT supply module when installed in a user-defined cabinet. Component designations used in the diagrams ■...
ACS-AP-x control panel Fxx.xx Fuses Main switch-disconnector Main contactor Rx.x Common mode filter LCL filter module (type ALCL-05-5) Supply module (type ACS880-204) ■ Frame R8i and multiples Designation Component Varistor board CVAR-01C in UL/CSA installations BCU control unit ACS-AP-x control panel Fxx.xx...
Example circuit diagrams 379 Circuit diagram set contents The contents of each circuit diagram set are listed below: ACS880-204 IGBT supply unit R1i…R4i with one supply module (3AXD10000314213) • Main fuse switch • IGBT supply module • LCL filter module WFU-xx •...
Product and service inquiries Address any inquiries about the product to your local ABB representative, quoting the type designation and serial number of the unit in question. A listing of ABB sales, support and service contacts can be found by navigating to www.abb.com/searchchannels.