Planning And Use; Operating Mode; Operating Mode Switching 1 Bit; Operating Mode Switching 1 Byte - ABB 2CSYK1201C Product Manual

Mylos knx
Table of Contents

Advertisement

MYLOS
Building Automation
®
7

Planning and use

This section contains tips and application examples for practical application of the device.
7.1

Operating mode

The ambient temperature controller has he following four operating modes:
For switching between the operating modes switching telegrams (parameter "operating mode switching": "1 bit
(3x)") or 1-byte value telegrams (parameter "operating mode switching": "1 byte (2x)") are used (see also drawings
of operating modes on page 83, Section Operating mode switching).
7.1.1

Operating mode switching 1 bit

The frost/heat protection has the top priority, i.e. in this case switching to a different operating mode is disabled.
Frost/heat protection must be disabled first, e.g. by closing an open window. Night mode has the next higher priority,
followed by comfort mode. If none of the above three operating modes are enabled, the ambient temperature
controller is in standby mode.
7.1.2

Operating mode switching 1 byte

When switching operating mode via 1 byte an object is available. When, for example, a comfort telegram is received,
the room thermostat switches to comfort mode. If a night telegram is received, the ambient temperature controller
switches to night mode. This object is controlled, for example, by time switches.
The following applies to the 1-byte communication object:
64 Planning and use | MYLOS
®
Comfort
object
Night
1
Comfort
0
Standby
Auto
Auto
Comfort
Comfort
operation
operation
Standby
Standby
operation
operation
Night
Night
operation
operation
Frost/Heat
Frost/Heat
Protection
Protection
operation
operation
Building Automation
Planning and use
Night
Frost Protection
object
Operating mode
Frost
1
1
0
0
1-Byte
1-Byte
operating
operating
mode switching.
mode switching.
Operating mode
Operating mode

Advertisement

Table of Contents
loading

This manual is also suitable for:

2csyk1201s

Table of Contents