Special Operating States - ABB 2CSYK1201C Product Manual

Mylos knx
Table of Contents

Advertisement

MYLOS
Building Automation
Commissioning
®
6.4

Special operating states

Behaviour after reset
The behaviour after reset can be set for the operating mode, the operating type and the fan stage. Heating, cooling
and the status of the object "switching heating/cooling" can be selected for the operating mode. When it is set to
"depending on object "switching heating/cooling"", the object state is queried via the bus when switching on or
after a reset. Comfort mode is default after reset, however Standby, Night mode or Frost/Heat Protection can also
be selected. The active fan stage after reset can be stage 1, 2 or 3. If no stage is to be active after reset, select the
setting "Off". The setting "Automatic" switches on the fan stage in accordance with the current control value.
MYLOS
Building Automation | Commissioning 63
®

Advertisement

Table of Contents
loading

This manual is also suitable for:

2csyk1201s

Table of Contents