MYLOS
Building Automation
®
Return inactive a fan stage of and automatic return not 0
Options:
- Yes
- No
If the user has manually changed the stage to "switch off", the ambient temperature controller can also be set so that
it does not return to automatic switching at the end of the "manual switching period" but rather remains switched off.
This parameter is only available if the "Heating" or "Heat and cool" control functions are used and the heating control
type is set to "FanCoil".
Threshold value stage 1
Options:
- 0%
- 10 %
- ...
- 50 %
- ...
- 100 %
Threshold value stage 1 specifies the magnitude of the control value required to switch the ambient temperature
controller to fan stage 1.
The threshold can be defined in percentages. Make sure that the threshold for stage 1 is not set higher than the
threshold for stage 2 (if available).
This parameter is only available if the "Heating" or "Heat and cool" control functions are used, the heating control
type is set to "FanCoil" and the number of fan stages is min. "1 stage".
Threshold value stage 2
Options:
- 0%
- 10 %
- ...
- 40 %
- ...
- 100 %
Threshold value stage 2 specifies the magnitude of the control value required to switch the ambient temperature
controller from fan stage 1 to fan stage 2. The threshold can be defined in percentages. Make sure that the threshold
for stage 1 is not set higher than the threshold for stage 2 (if available). This parameter is only available if the "Heating"
or "Heat and cool" control functions are used, the heating control type is set to "FanCoil" and the number of fan
stages is min. "2 stage".
Threshold value stage 3
Options:
- 0%
- 10 %
- ...
- 70 %
- ...
- 100 %
Threshold value stage 3 specifies the magnitude of the control value required to switch the ambient temperature
controller from fan stage 2 to fan stage 3. The threshold can be defined in percentages. Make sure that the threshold
for stage 3 is not set higher than the threshold for stage 3 (if available).
This parameter is only available if the "Heating" or "Heat and cool" control functions are used, the heating control
type is set to "FanCoil" and the number of fan stages is min. "3 stage".