MYLOS
Building Automation
Commissioning
®
Send setpoint cyclic (0 – inactive, min)
Options: - 0 .. 60
If the current value is to be sent cyclically independent of a change, the parameter "Send setpoint cyclic" must be
set to a time. This may be necessary, for instance, with a higher-level boiler that expects to receive setpoints and
current values within a certain time period. If values are not received, a predefined supply line temperature is set that
is no longer oriented on actual demand.
MYLOS
Building Automation | Commissioning 23
®