Parameter Window "Additional Heating - ABB 2CSYK1201C Product Manual

Mylos knx
Table of Contents

Advertisement

MYLOS
Building Automation
®
6.1.6

Parameter window "Additional heating"

Control type
Options:
- 1 bit control
- 1 byte control
The additional heating stage can send a 1-bit or 1-byte control value. If "1-bit Switching" is selected, the additional
stage controls a switching command (1-bit) via a 1-bit communication object, e.g. a thermoelectric actuator that
controls a switching actuator. If "1-bit continuous" is selected, the additional stage carries out a continuous control
(1-bit) via a 1-bit communication object, e.g. an electric drive or an actuator with integrated pulse-width modulation.
This parameter is only available if the "Heating" or "Heat and cool" control functions are used.
Invert control value
Options:
- Yes
- No
"Invert heating" is used to adjust the direction of control action of the control value to "de-energised open" or "de-
energised closed" valves. This parameter is only available if the "Heating" or "Heat and cool" control functions are used.
Hysteresis
Options:
- 0.0°C
- 0.1°C
- 0.2°C
- 0.3°C
- .........
- 1.0°C
- .........
- 2.0°C
30 Commissioning | MYLOS