ABB 650 series Engineering Manual page 73

Hide thumbs Also See for 650 series:
Table of Contents

Advertisement

1MRK 511 261-UEN -
650 series
Engineering Manual
Prio 1 = RED
Prio 2 = YELLOW
Prio 3 = GREEN
When RED and YELLOW are ON at the same time, the LED will
illuminate in RED.
The operator's acknowledge for the LED signals is done for all three
signals (RED, YELLOW, GREEN) of the LED.
A reset of the LLEDs operates also on all three signals of the LEDs.
Follow-S
The LED illumination follows the status of the signal. The LED
illuminates steady (S).
Follow-F
The LED illumination follows the status of the signal. The LED
illuminates flashing (F).
LatchedAck-F-S
The LED latches the signal change OFF-ON and flashes (F) until it is
acknowledged.
When the signal is still ON at the time the signal is acknowledged the
LED changes to steady (S) mode.
When the signal has already changed to OFF before the time it is
acknowledged, the LED turns to OFF.
LatchedAck-S-F
The same as LatchedAck-F-S but the LED starts with steady state and
flashes after acknowledgment.
LatchedColl-S
The LED illuminates in all cases in steady mode only
The LED latches a signal change from OFF-ON until it is acknowledged
by the operator.
The LED stays in steady mode when it is reset and the signal is still in
ON state.
The LED is OFF only after the signal has changed to OFF state AND it
is reset by the operator via 'Clear' operation.
LatchedReset-S
This mode is used for all LEDs that are used to indicate a disturbance.
The LEDs will stay in the last state after the disturbance run time until
they are reset after a defined time.
The timers are set in Parameter Setting tool in the function block LEDGEN.
Section 6
Local HMI engineering
67