Importing Scl Files To Pcm600; Importing Scd Files - ABB 650 series Engineering Manual

Hide thumbs Also See for 650 series:
Table of Contents

Advertisement

1MRK 511 261-UEN -
7.5
7.5.1
650 series
Engineering Manual
Please see the IET600 user manual for additional information about
vertical and horizontal station communication engineering.

Importing SCL files to PCM600

The IED engineering tool must be able to receive a SCD file or an ICD file as
import to receive the engineered communication extensions, for example for the
different IEDs.

Importing SCD files

Procedure to import a SCD file to PCM600:
1.
Select the station in the plant structure.
2.
Right-click the station and select Import ...
3.
Select the file to be imported from the open standard Windows menu and start
the reading.
4.
A SCL Import Options window opens, which queries how the file should be
handled during import, see
IEC09000631 V1 EN
Figure 68:
IEC 61850: Import SCD file
4.1. Click Ignore Substation Section to not import the "SSD-file" part of the
SCD-file.
4.2. Click Don't import IEDs of unknown type to protect the existing IEDs in
case the SCD file does not match the original configuration in PCM600.
4.3. Click Replace unknown ... can be used when it is known, that the file
includes additional IEDs that are needed. The IED of type "Generic IEC
IEC 61850 communication engineering
Figure
68.
IEC09000631-1-en.vsd
Section 7
95