ABB 650 series Engineering Manual page 71

Hide thumbs Also See for 650 series:
Table of Contents

Advertisement

1MRK 511 261-UEN -
650 series
Engineering Manual
B
IEC12000612 V1 EN
Figure 43:
Local HMI: Placement of local HMI operation elements
Function block LEDGEN
Handles an external acknowledge signal as source to acknowledge the LEDs.
Generates an additional pulse for general purposes whenever the LEDs are
acknowledged by the operator.
Generates a pulse whenever a new LED signal occurs. It may be used to
trigger an acoustical alarm.
Handles the timer tReset and tMax for the LED operation mode 'LatchedReset-
S'.
Function block GRP1_LED1 to GRP3_LED15
The 15 LEDs on the right side of the LCD can indicate in total 45 alarms,
warnings or other signals to the operator. They are organized in three groups 1
to 3.
Each signal group belongs to one function block.
Each LED illuminates in one of the three colors: RED, YELLOW or GREEN.
The organization of flashing, acknowledgment and group selection is done
directly between the function blocks and the basic LHMI keys, the
'Multifunction' key [a] to toggle between the three groups or the 'Clear' key [b]
to acknowledge or reset the LEDs.
Only the programming of the signals is needed for the LEDs.
The operation mode of the LEDs is defined in Parameter Setting tool.
Function block FNKEYMD1 to 5
Every function key has an own FNKEYMD function block.
The 5 function keys on the left side of the LCD [B] can be used to process
demands.
The function block handles the signal for the LED included in the key as input
signals.
The LED signal of the key is independent of the key function and must be
programed to process demands.
The function block handles the operators command when the key is pressed as
output signal.
Local HMI engineering
A
Section 6
65

Advertisement

Table of Contents
loading