COM600 Station Automation Series
User's Guide
OPC client properties to the data objects below an OPC Server. Note that the name of
the data object should be the same as specified in the client object's Data Object Properties
and it specifies to which client instance that property belongs. This property, together
with the station address on the data object, connects the data object to a specific OPC
client. The protocol used defines which properties are added to a particular object. Refer
to the respective client and server user's guides listed in 1.8, Related documents.

SCL Import function

You can import the communication structure under of an OPC Server, Client or IED
with configurations from an existing file. This is done using the SCL import function.
If an OPC Server or client configuration file is used, then the whole communication
structure is imported. Configurations can be imported for single IEDs, by selecting an
IED object.
The file extensions for the import files can be .icd, .cid, .scd or .xml.
To import a configuration file:
1. Right-click the IEC 61850 OPC Server or IED and select SCL Import from the
shortcut menu.
2. Click Select File.
3. Browse for a new configuration file from the dialog that opens.
4. Select the file and click Open.
5. Select the device to import from the drop-down menu. You can preview the config-
uration from the Objects tab.
6. Click Import.
The new preconfigured objects will appear in the object tree. If the configuration file is
very large the import may take time.
Figure 4.3.3.2-1 Example of IEC 61850 OPC Server SCL Import