Mitsubishi Electric FR-A820-00046 Instruction Manual page 35

Hide thumbs Also See for FR-A820-00046:
Table of Contents

Advertisement

Installation and wiring
NOTES
The above shows a selection example for the ND rating. For selecting the SLD rating, LD rating, or
HD rating, refer to the Technical News (MF-X-121) contained in the enclosed CD-ROM.
When the inverter capacity is larger than the motor capacity, select an MCCB and a magnetic
contactor according to the inverter model, and select cables and reactors according to the motor
output.
When the breaker on the inverter's input side trips, check for the wiring fault (short circuit), dam-
age to internal parts of the inverter etc. The cause of the trip must be identified and removed
before turning ON the power of the breaker.
400 V class
Motor
output
[kW]
0.4
0.75
1.5
2.2
3.7
5.5
7.5
11
15
18.5
22
30
37
45
55
75
90
110
132
160
185
220
250
280
Tab. 2-3:
Assumes the use of a Mitsubishi 4-pole standard motor with the power supply voltage of 400 V AC
50 Hz.
FR-A800
Molded case circuit breaker (MCCB) or
earth leakage circuit breaker (ELB)
Applicable inverter
model
Power factor improving (AC or DC)
FR-A840-00023(0.4K)
FR-A840-00038(0.75K)
FR-A840-00052(1.5K)
FR-A840-00083(2.2K)
FR-A840-00126(3.7K)
FR-A840-00170(5.5K)
FR-A840-00250(7.5K)
FR-A840-00310(11K)
FR-A840-00380(15K)
FR-A840-00470(18.5K)
FR-A840-00620(22K)
FR-A840-00770(30K)
FR-A840-00930(37K)
FR-A840-01160(45K)
FR-A840-01800(55K)
FR-A840-02160(75K)
FR-A840-02600(90K)
FR-A840-03250(110K)
FR-A840-03610(132K)
FR-A840-04320(160K)
FR-A840-04810(185K)
FR-A840-05470(220K)
FR-A840-06100(250K)
FR-A840-06830(280K)
Breakers and contactors (400 V class)
(NF, NV type)
reactor
Without
With
5A
5A
5A
5A
10A
10A
10A
10A
20A
15A
30A
20A
30A
30A
50A
40A
60A
50A
75A
60A
100A
75A
125A
100A
150A
125A
175A
150A
200A
175A
225A
225A
225A
400A
400A
400A
500A
600A
600A
Peripheral devices
Input-side magnetic contactor
Power factor improving (AC or DC)
reactor
Without
With
S-T10
S-T10
S-T10
S-T10
S-T10
S-T10
S-T10
S-T10
S-T10
S-T10
S-T21
S-T12
S-T21
S-NT21
S-T21
S-T21
S-N25
S-T21
S-N25
S-N25
S-N35
S-N25
S-N50
S-N50
S-N65
S-N50
S-N80
S-N65
S-N80
S-N80
S-N95
S-N150
S-N180
S-N220
S-N300
S-N300
S-N400
S-N600
S-N600
2 - 5

Hide quick links:

Advertisement

Table of Contents
loading