Controllable Integer Status (Inc) - ABB COM600 3.4 User Manual

Station automation
Hide thumbs Also See for COM600 3.4:
Table of Contents

Advertisement

5.2.14.
Name
Type
ctlVal
INTEGER
stVal
INTEGER
q
Quality
t
TimeStamp
d
Description
5.2.15.
Name
Type
ctlVal
ENUMERATED
valWTr
ValWithTrans
q
Quality
t
TimeStamp
d
Description
5.2.16.
Name
Type
ctlVal
INTEGER
valWTr
ValWithTrans
q
Quality
t
TimeStamp
d
Description
62
Station Automation COM600 3.4
IEC 60870-5-101 Slave (OPC) User's Manual

Controllable integer status (INC)

INC represents DMCD M_ME_NA_1, M_ME_TA_1, M_ME_TD_1, M_ME_NB_1,
M_ME_TB_1, C_SE_NA, C_SE_NB_1.
Value/ Value
range
Text
Binary controlled step position information (BSC)
BSC represents DMCD M_ST_NA_1, M_ST_TA_1, M_ST_TB_1, M_RC_NA_1.
Value/ Value
range
stop (0)
lower (1)
higher (2)
reserved (3)
Text
Integer controlled step position information (ISC)
ISC represents C_SE_NA_1, C_SE_NB_1, M_ST_NA_1, M_ST_TA_1, M_ST_TB_1.
Value/ Value
range
-64 ... 63
Text
Mandat-
Protocol informa-
ory/Optional
tion element
M
NVA
M
VAI32
M
BL, SB, NT, IV
M
CP24TIME2A
O
Mandat-
Protocol informa-
ory/Optional
tion element
M
RCO
M
VTI
M
BL, SB, NT, IV
M
CP24Time2a
O
Mandat-
Protocol informa-
ory/Optional
tion element
M
NVA
M
VTI
M
BL, SB, NT, IV
M
CP24TIME2A
O
1MRS755382
OPC data types
VT_I4
VT_I4
VT_I4
VT_DATE
VT_BSTR
OPC data types
VT_I1
VT_I4
VT_I4
VT_DATE
VT_BSTR
OPC data types
VT_I4
VT_I4
V_I4
V_DATE
VT_BSTR

Advertisement

Table of Contents
loading

Table of Contents