Analogue Set Point (Apc) - ABB COM600 3.4 User Manual

Station automation
Hide thumbs Also See for COM600 3.4:
Table of Contents

Advertisement

1MRS755382
3.4.5.17.
Station Automation COM600 3.4
IEC 60870-5-101 Slave (OPC) User's Manual
Property/ Para-
Value or Value range/ Default
meter
Over Write
True = 1
False = 0
Default: False = 0
Priority
0...3
End of queue = 0
Middle = 1, 2
Beginning of queue = 3
Update Rate
0...60000
Default: 0
Data Class Spe-
cific
Send Indication As
Send with normalized value =
Value Type
0
Send with scaled value = 1
Time Tag Handling
Do not Send Time Tag = 0
Send Short Format Time Tag
= 1
Send Long Format Time Tag =
2
Default: Send Long Format
Time Tag

Analogue set point (APC)

Table 3.4.5.17-1 Configurable APC properties for OPC client
Property/ Para-
Value or Value range/ Default
meter
Basic
Common Data
APC
Class
Addresses
Command Address
0...16777215
Description
Defines whether a new indication value
overwrites an older one in the queue.
Priority of ASDU. This property defines
how the ASDU sent is placed in the class
1 and class 2 queues.
Maximum update rate of indication
changes between OPC server and client
in milliseconds. 0 means that server sends
all the changes to the client.
Specifies if the value of indication signal
is sent as normalized or scaled. Long
timestamp format cannot be used with a
scaled value.
Specifies the format of timestamp if one
is used: none, short, or long. Long time
tag format cannot be used with a scaled
value.
Description
Common data class according to IEC
61850.
IEC address for command.
51