Controllable Integer Status (Inc) - ABB COM600S User Manual

Com600 series, modbus tcp master, opc
Hide thumbs Also See for COM600S:
Table of Contents

Advertisement

3.4.8.11.
54
COM600 series, Version 4.1
Modbus TCP Master (OPC) User's Manual
Table 3.4.8.10-2 Configurable DPS properties for OPC servers with Modbus device,
subtype BIT_DPU_IN_REGISTER
Property/Para-
Value or Value range/ Default
meter
/Example
Basic
61850-Type
DPS
Subtype
BIT_DPU_IN_REGISTER
Addresses
Bit Mask for Fail
0 - 65535
Alarm
Default 0
Bit Mask for Inverse
0 - 65535
status
Default 0
Bit Mask For Status
0 - 65535
Default: 0
Fail Alarm register
0 - 65535
Default 0
Indication Register
0 - 65535
Default 0
Inverse status
0 - 65535
register

Controllable integer status (INC)

Controllable Integer Status (INC) for OPC server with Modbus IED supports the following
subtypes:
REGISTER_BASED_CONTROL
DPU_REGISTER_BASED_CONTROL
Description
61850-Type
Bit mask for fail alarm
Bit mask for inverse status
Bit mask for status.
Holding address for the Fail alarm. Holding
register = 4x reference address range
40001 - 49999 .
Address 0 equals to no information avail-
able.
Holding address for the Fail alarm. Holding
register = 4x reference address range
40001 - 49999 .
Address 0 equals to no information avail-
able.
Holding address for the Fail alarm. Holding
register = 4x reference address range
40001 - 49999 .
Address 0 equals to no information avail-
able.