Station Automation COM600 3.4
IEC 60870-5-101 Slave (OPC) User's Manual
Property/ Para-
Value or Value range/ Default
meter
Time Tag Handling
Do not Send Time Tag = 0
Send Short Format Time Tag
= 1
Send Long Format Time Tag =
2
Default: Send Long Format
Time Tag
WYE
Table 3.4.5.10-1 Configurable WYE properties for OPC client
Property/ Para-
Value or Value range/ Default
meter
Basic
Common Data
WYE
Class
Addresses
Neutral Address
0...16777215
0 = Not in use
Phase A Address
0...16777215
0 = Not in use
Phase B Address
0...16777215
0 = Not in use
Phase C Address
0...16777215
0 = Not in use
Net Address
0...16777215
0 = Not in use
Res Address
0...16777215
0 = Not in use
Common
Class
Class 1 = 1
Class 2 = 2
Default: Class 2 = 2
Description
Specifies the format of timestamp if one
is used: none, short, or long. Long time
tag format cannot be used with a scaled
value.
Description
Common data class according to IEC
61850.
IEC address for neutral.
IEC address for phase A.
IEC address for phase B.
IEC address for phase C.
IED address for net.
IED address for res.
Class of ASDU. Data sent from the slave
to the master can be assigned to two
classes: class 1 and class 2. Data in class
1 is sent with higher priority than data in
class 2.