DNP 3.0 Serial Slave (OPC) User's Manual
Figure 4.3-2 Event log file

DNP Serial Channel diagnostics

The DNP Serial Channel activity can be monitored with the Online diagnostics function.
You can also take a channel into use or out of use as described in this section.
To monitor and control DNP Serial Channel activity:
1.
Select the channel you want to monitor in the object tree of SAB600.
2.
Right-click the channel.
3.
Select Online diagnostics.
In the Diagnostic counters field, you can monitor the channel activity. To reset Diagnostic
counters, click Reset counters.
You can take a DNP Serial Channel into use by marking the In use check box. If you
unmark the check box, the channel is taken out of use. To manually update diagnostic
counters, click Refresh.
For more information on the channel online diagnostics with the Analyzer function, see
COM600 User's manual.

DNP Serial IED diagnostics

The DNP Serial IED communication can be monitored with the Online diagnostics
function. You can also take a device into use or out of use as described in this section.
To monitor and control DNP Serial IED communication:
1.
Select the device you want to monitor in the object tree of SAB600.
2.
Right-click the device.
3.
Select Online diagnostics.
In the Status information field, you can monitor the device status.
The Diagnostic counters field provides information on device activity. To reset diagnostic
counters, click Reset counters.