1MRS755495
COM600 series, Version 5.0
DNP 3.0 Serial Slave (OPC) User's Manual
Property/ Para-
Value or Value range/ Default
meter
Class
Class 0...3
Default: Class 0
Update Rate
0...65535
Default: 0
Data Class Spe-
cific
Indication Object
Binary input (1, 2)
Binary output (10)
Default: Binary input (1, 2)
Send All Updates
True
False
Default: False
Send As Inverse
True
Value
False
Default: False
Send As Single
True
Point
False
Default: False
Time And Type
Send as static data (always
Variation
without time)
Event without time
Event with time
Event with relative time (valid
for binary inputs only)
Default: Event with time
Description
Class of ASDU. Data sent from the slave
to the master can be assigned to four
classes. Data in class 1 is sent with higher
priority than data in class 3.
Maximum update rate of signal state
changes between the OPC server and
client in milliseconds. 0 means that the
server sends all the changes to the client.
Object number for indication.
Defines if all changes in value are sent to
the master.
Defines if the value of a message is
inverse.
Defines if a value is sent as single point.
Specifies the type of the timestamp a
message is sent with.