Download Print this page

ABB i-bus KNX Product Manual page 42

Fan coil/systemised building technology
Hide thumbs Also See for i-bus KNX:

Advertisement

6
G lossary
5 B
6.1
C ontinuous and switching control
2 0 B
A switching (2-point) control detects only 2 status conditions; or on off.
A continuous control works with a set value between 0% and 100% and can
therefore dose the energy supply precisely. This achieves convenient and precise
control.
6.2
H ysteresis
2 1 B
The hysteresis determines the difference between switch-on and switch-off
temperature with a controller. It can be both positive and negative.
With a combination of heating and cooling control, it affects the amount of the
zone
.
U H
Without hysteresis, the controller would switch on and off without interruption as long
as the temperature is in the range of the set value.
6.2.1
N egative hysteresis:
5 0 B
Heating: The heating is carried out until the set value is reached.
The heating is only switched on again when the temperature has fallen below the
threshold set value hysteresis.
Cooling: Cooling is carried out until the set value – hysteresis threshold is reached.
The system is only switched on again if the temperature has risen above the set
value.
Cooling example:
Cooling with set value 25 °C, hysteresis = 1°C and ambient temperature 27 °C.
The cooling is switched on and only switches back off again once a temperature of
24 °C (25 °C – 1 °C) is reached.
Once the temperature rises above 25 °C, the system is switched back on again.
6.2.2
P ositive hysteresis
5 1 B
Heating is carried out until the temperature reaches the set value + hysteresis
threshold.
The heating is only switched on again if the temperature has dropped below the set
value.
Heating example:
Heating with set value 20°C, hysteresis = 1°C and ambient temperature 19 °C.
The heating is switched on and only switches back off again once a temperature of
21 °C (20 °C – +1 °C) is reached.
d ead
H U
42

Advertisement

loading