Object 2 "actual value"
This object sends the temperature currently measured by the sensor (if sending is
permitted by the parameter settings)
Object 3 "Operating mode preselection" / "Night < - > Standby"
The function of this object is dependent on the Objects for setting the operating mode
parameter on the parameter page
Objects for setting the operating
mode
n ew: Operating mode, presence,
H U
window status
U H
o ld: Comfort, Night, Frost
H U
• Object 4 "Presence" / "Comfort"
The function of this object is dependent on the Objects for setting the operating mode
parameter on the parameter page
Objects for setting the operating
mode
n ew: Operating mode, presence,
H U
window status
U H
o ld: Comfort, Night, Frost
H U
O perating mode
H U
Function of the object
1 byte object for selecting one of 4 operating
modes.
1 = comfort, 2 = standby, 3 = night,
4 = Frost protection (heat protection)
If a different value is received (0 or >4), the
comfort operating value is activated.
The details in brackets relate to cooling
operation
With this setting, this object is a 1Bit object.
U H
This means that the Night or Standby operating
mode can be activated
0=Standby 1=Night
o perating mode
H U
Function of the object
Presence:
This object can be used to receive the status of
a presence watchdog (e.g. button, movement
sensor).
A 1 to this object activates the Comfort
operating mode.
Comfort:
U H
A 1 to this object activates the Comfort
operating mode.
This operating mode has priority over night and
standby modes.
The comfort mode is deactivated again by
sending a 0 to the object.
.
U H
.