ABB i-bus KNX Product Manual page 40

Fan coil/systemised building technology
Hide thumbs Also See for i-bus KNX:

Advertisement

5.5.2
B ehaviour of the P controller
4 8 B
Max. 4l/Min.
21l
Strip width
17l
15l
If the filling quantity is 15l, a control deviation is produced of 21l – 15l = 6l
As our actual value is outside the strip width, the controller will actuate the supply
with 100%
i.e. at 4l / minute.
The supply quantity (= control value) is calculated using the control deviation
(set value – actual value) and the strip width.
Control value = (control deviation / strip width) x 100
The table below clearly explains the behaviour and therefore also the limits of the P
controller.
Filling level
Control value
15l
100%
19l
50%
20l
25%
In the last line, it is clear that the filling level cannot increase any more because the
supply is allowing exactly the amount of water that can flow out again via losses.
The result is a consistent control deviation of 1l, the set value can never be reached.
If the losses were 1l higher, the remaining control deviation would increase by the
same amount and the filling level would never exceed the 19l mark.
In a room, this would mean that the control deviation increases with a falling outside
temperature.
Set value
Actual value
Losses
1l/Min
Supply
Losses
4 l/min
2 l/min
1 l/min
Supply filling level
3 l/min
1 l/min
1 l/min
0 l/min