ABB i-bus KNX Product Manual page 35

Fan coil/systemised building technology
Hide thumbs Also See for i-bus KNX:

Advertisement

5.4
E xternal interface
1 8 B
The external interface is activated on the Settings parameter page.
It consists of the 3 inputs E1, E2 and E3.
E1 and E2 are purely binary inputs, E3 can be used both as a binary input and as an
analogue input for an external temperature sensor.
All 3 inputs are connected in the base via the connection terminals
The following functions can be realised:
• Switching (1 switch or button)
• Blind up/down (with 2 buttons on E1 + E2)
• One-panel blind operation (with 1 button)
• Dimming brighter/darker (with 2 buttons on E1 + E2)
• One-panel dimming operation (with 1 button)
If the blind and dimming functions are implemented via 2 buttons, E1 and E2 are
automatically connected with one another and act jointly on objects 9, 10 and 12.
5.4.1
O verview: Function of objects 9 .. 14.
4 1 B
Function of E1
Function of E1
Switch
Blind UP
Note: E2 is
automatically set to
blind DOWN.
One-panel blind
operation
Brighter dimming
Note: E2 is
automatically set to dim
darker
One-panel dimming
operation
Object 9
sends the switch
status of the E1
input
Sends commands
for step/stop in the
up direction or slat
positioning
Sends commands
for step/stop or slat
positioning
Sends on/off
commands to the
dimmer
Sends on/off
commands to the
dimmer
Function
Object 10
Not used
Not used
Sends up/down
command to blind
Not used
Sends 4 bit
dimming commands
Object 12
Not used
Sends up command
to blind
Not used
Sends 4 bit
dimming commands
Not used
35