3.4.3
C ooling set values
2 9 B
This page only appears if on the parameter page Settings the control function
Heating and cooling has been selected (userdefined control).
Table 2
Designation
Dead zone between
heating and cooling
Raising in standby mode
(for cooling)
Raising in night mode (for
cooling)
Set value for heat
protection mode (for
cooling)
Values
1 K
2 K
3 K
4 K
5 K
6 K
0.5 K, 1 K, 1.5 K
2 K, 2.5 K, 3 K
3.5 K, 4 K
3 K, 4 K, 5 K
6 K, 7 K, 8 K
42 °C (i.e. roughly
equates to no heat
protection)
29 °C, 30 °C, 31 °C,
32 °C, 33 °C, 34 °C,
35 °C
Meaning
Specifies the buffer zone
between the set values for
heating and in cooling
mode.
With a switching (2-point)
control, the dead zone is
increased via the
hysteresis.
See in glossary:
D ead
H U
zone
U H
In cooling mode, the
temperature is raised in
standby
see Raising in standby
mode
The heat protection
represents the maximum
temperature permitted for
the controlled area. With
cooling it fulfils the same
task as the frost protection
mode during heating, i.e.
save energy and at the
same time prevent non-
permissible temperatures.