Transmitter Power Supply Module; Relays; Modbus/Digital Input - ABB SM500F User Manual

Field mountable paperless recorder
Hide thumbs Also See for SM500F:
Table of Contents

Advertisement

SM500F
Field mountable paperless recorder

2.7 Transmitter Power Supply Module

One transmitter power supply module can be fitted in position D to provide a nominal 24V supply capable
of driving two, 2-wire transmitters.
Fig. 2.12 Transmitter Power Supply Module
Note. Analog input terminal screws must be tightened to a torque of 0.5 Nm (4.5 lbf.in).

2.8 Relays

One relay is provided as standard (position E). An additional relay module can be fitted in position D to
provide two additional relays.
The maximum individual relay current is 5A.
Relay contacts are fitted with arc suppression components as standard.
Set the polarity using the relay links provided on the recorder's motherboard (for the standard relay) and the
relay module board (for the optional additional relays) – see Fig. 2.8, page 17.

2.9 Modbus/Digital Input

A Modbus/digital input module can be fitted in position F to provide a 2-wire isolated RS485 interface and
2 digital inputs.
Fig. 2.13 Modbus/Digital Input Module
IM/SM500F Rev. Z
2-wire Transmitter Power Supply
(24V DC, 22mA max.)
+
Analog Input
1
2
3
4
Rx/Tx +
Rx/Tx –
GND
Dig In 1
Dig In 2
Common
2 Installation
21

Advertisement

Table of Contents
loading

Table of Contents