7.11.2 Comms Analog Input

Note. This tab is displayed only if only if 'Implementation' on the 'Modbus TCP' tab is set to 'Modbus
TCP Client' – see page 125.
IM/SM500F Rev. Z
Select the comms analog input to hold the data from the nominated slave
device.
Select the communications protocol to be used by the recorder to
communicate with a nominated slave device:
None – comms analog channel unused
TCP – Modbus Transmission Control Protocol
RTU – access a Remote Terminal Unit (RTU) via Modbus TCP
gateway
Note. Displayed only if 'Protocol' is set to 'TCP'.
Enter the IP address assigned to the slave device.
Note. Displayed only if 'Protocol' is set to 'RTU'.
Enter the RTU address assigned to the remote unit (1 to 247).
Note. Displayed only if 'Protocol' is set to 'RTU'.
Set the IP address for the Modbus TCP gateway for connection to the
RTU.
Note. Displayed only if 'Protocol' is set to 'TCP' or 'RTU'.
Enter the register number to be read in the slave device.
Note. Displayed only if 'Protocol' is set to 'TCP' or 'RTU'.
Select the register type, 'Holding Register' or 'Input Register'.
7 Configuration
127