HMI Configuration Manual
Do not add connectivity nodes to the connection between
the busbar and the bay switchgears.
Do not add connectivity nodes between the earth symbol
and the switchgear object (disconnector).
To connect a power transformer to another bay, create a
connectivity node in the target bay (not in the bay where
the power transformer is located).
Default relative sizes of the symbols can be configured
using the Settings tool of the Gateway object. Default
values can be overriden for individual symbol instances
with the Relative Size property of the symbol instance.
This makes it possible to have individual sizes for sym-
bols in the SLD.
5. Add Via points, if you want the line to follow a certain route.
6. Connect objects
Activate the Direct Link tool from the tool bar.
Link two objects together by selecting their link points.