Enervista Software; Software Settings Templates; Introduction - GE D90 Plus Instruction Manual

Line distance protection system
Hide thumbs Also See for D90 Plus:
Table of Contents

Advertisement

D90
Chapter 5: EnerVista software

Introduction

Settings templates
PLUS
D90
LINE DISTANCE PROTECTION SYSTEM – INSTRUCTION MANUAL
Plus
Line Distance Protection System

EnerVista software

This chapter describes the EnerVista UR
Plus
The EnerVista UR
Setup software provides a graphical user interface (GUI) to configure,
monitor, maintain, and troubleshoot the operation of UR
locally to a computer or over local or wide area communications networks. The software
can be initiated in either offline (not communicating) or online (communicating) modes
Plus
with a UR
-series device. In offline mode, a device settings file can be created or
configured for eventual downloading to that device. In online mode, the settings and
Plus
actual values of a UR
communications. The software provides the tools to integrate information measured by
Plus
the D90
into DCS or SCADA monitoring systems. Convenient COMTRADE and sequence
of events viewers are integrated. This allows the user to carry out post-mortem event
analysis to ensure proper protection system operation.
Settings file templates simplify the configuration and commissioning of multiple devices
that protect similar assets. An example is a substation that has 10 similar feeders
Plus
protected by 10 UR
In these situations, typically 90% or greater of the settings are identical among devices.
The templates allow engineers to configure and test these common settings, then lock
them so that they are not available to users. For example, locked settings can be hidden
from view for field engineers, allowing them to quickly identify and concentrate on specific
settings.
The remaining settings (typically 10% or less) can be specified as editable and made
available to field engineers installing the devices. These are settings such as protection
element pickup values and CT and VT ratios.
Plus
Setup software.
-series device can be configured or monitored utilizing real-time
-series relays.
Plus
-series devices connected
81

Advertisement

Table of Contents
loading

Table of Contents