Annunciator Configuration - GE D90 Plus Instruction Manual

Line distance protection system
Hide thumbs Also See for D90 Plus:
Table of Contents

Advertisement

CHAPTER 12: LOCAL INTERFACE

Annunciator configuration

PLUS
D90
LINE DISTANCE PROTECTION SYSTEM – INSTRUCTION MANUAL
Figure 509: Annunciator alarm sequence
The table outlines annunciator states.
Table 41: Acknowledgeable alarm states
Sequence (initial
Process (status)
state)
Normal
Normal
Normal
Abnormal
Alarm
Normal
Alarm
Normal
Alarm
Abnormal
Acknowledged
Abnormal
Acknowledged
Normal
Ringback
Normal
Ringback
Abnormal
The visual indications display as follows:
Off — Grey text on a darker grey background
On — User-configurable
Fast flash — Alternating between off and on state two times per second
Slow flash — Alternating between off and on state one time per second
In the event of an alarm, the page containing the alarm is promoted to active page. If there
are multiple pages with alarms, the page with the lowest page number is promoted.
If there are alarms on multiple pages, and alarms on some pages have already been
acknowledged (but not cleared) by the user, then the pages with active alarms move ahead
of the pages that have acknowledged alarms. The user always has to navigate through the
pages of alarms to view them.
Display of alarm pages is prioritized according to active window (unacknowledged or
flashing alarm) and page number (for example, if two pages have an unacknowledged
alarm, the page with the lowest number is promoted automatically as the displayed page).
Select the Settings > Local HMI > Annunciator Panel menu to open the annunciator
configuration window.
Pushbutton
Sequence (final
(input)
state)
N/A
N/A
N/A
Alarm
N/A
Alarm
Acknowledged
Normal
Acknowledged
Acknowledged
N/A
Acknowledged
N/A
Ringback
Reset
Normal
N/A
Acknowledged
ANNUNCIATOR PANEL
Visual indication
Off
Fast flash
Fast flash
Off
On
On
Slow flash
Off
On
583