INTER-RELAY COMMUNICATIONS
166
Select the Actual Values > Communications > Inter-Relay Transceivers menu to open
the inter-relay communication actual values window.
Figure 150: Inter-relay communication actual values
The following actual values are available for each channel.
Transceiver Temperature
Range: –99.99 to 300.00 °C
This value indicates the fiber transceiver temperature.
Transceiver Temperature Trouble
Range: On, Off
This value indicates whether the fiber transceiver temperature has exceeded the
manufacturer's limit.
Transceiver Voltage
Range: 0.0000 to 6.5535 V in steps of 0.0001
This value indicates the fiber transceiver voltage.
Voltage Trouble
Range: On, Off
This value indicates whether the fiber transceiver voltage level is outside the
manufacturer's limit.
Transmit Bias Current
Range: 0 to 65535 μA in steps of 1
This value indicates the fiber transceiver bias current level.
Transmit Bias Current Trouble
Range: On, Off
This value indicates whether the fiber transceiver bias current is outside the
manufacturer's limit.
Transmit Power Level
Range: –3276.8 to 3276.8 dBm in steps of 0.1
This value indicates the fiber transceiver transmitter power level.