CHAPTER 7: PROTECTION
NOTE:
FlexCurve software features
PLUS
D90
LINE DISTANCE PROTECTION SYSTEM – INSTRUCTION MANUAL
Figure 319: FlexCurve configuration settings
The following settings are available for each custom FlexCurve.
FlexCurve Name
Range: up to 20 alphanumeric characters
Default: FlexCurve A
This setting specifies a user-defined name for the FlexCurve.
Initialize From
Range: IEEE Moderately Inverse, IEEE Very Inverse, IEEE Extremely Inverse, IEC Curve A, IEC
Curve B, IEC Curve C, IEC Short Inverse, IAC Extreme Inv, IAC Very Inverse, IAC Inverse, IAC
Short Inverse, I Squared T, Recloser Curve, FlexCurve A, FlexCurve B, FlexCurve C,
FlexCurve D
Default: IEEE Moderately Inverse
This setting specifies a curve to use as a base for a custom FlexCurve. When the
Initialize FlexCurve button is clicked, the pickup settings are populated with values
specified by the curve selected in this setting.
0.00 × Pickup, 0.05 × Pickup,..., 20.00 × Pickup
Range: 0 to 65535 ms in steps of 1
Default: 0 ms
These settings specify the time to reset and operate at the following pickup levels: 0.00
to 0.98 and 1.03 to 20.00. This data is converted into two continuous curves by linear
interpolation between data points. To enter a custom FlexCurve, enter the reset or
operate time for each selected pickup point.
Take care when setting the two points that are close to the multiple of pickup of 1, that is,
0.98 pu and 1.03 pu. It is recommended to set the two times to a similar value, otherwise
the linear approximation can result in undesired behavior for the operating quantity that is
close to 1.00 pu.
The EnerVista software allows for easy configuration and management of FlexCurves and
their associated data points. Click the View FlexCurve button to graphically display the
selected FlexCurve.
CONTROL ELEMENTS