CONTROL ELEMENTS
340
A reclose initiate signal sends the scheme into the reclose-in-progress (RIP) state and
asserts the
operand. Once the breaker has opened, the scheme is latched into the
AR RIP
reclose-in-progress state and resets only when an
(autoreclose breaker 2) operand is generated or the scheme goes to the
AR CLS BKR 2
lockout state.
Figure 278: Autoreclose enable logic
Figure 279: Autoreclose initiate logic
AR CLS BKR 1
PLUS
D90
LINE DISTANCE PROTECTION SYSTEM – INSTRUCTION MANUAL
CHAPTER 7: PROTECTION
(autoreclose breaker 1) or