GGIO2 control configuration

PLUS
D90
LINE DISTANCE PROTECTION SYSTEM – INSTRUCTION MANUAL
display screens. Buffered reporting should generally be used for SOE logs since the
buffering capability reduces the chances of missing data state changes. Use unbuffered
reporting for local status display.
Select the Settings > Communications > IEC 61850 > GGIO1 Status Configuration menu
to open the GGIO1 status configuration window.
Figure 107: IEC 61850 GGIO1 status configuration
The following settings are available.
Number of Status Points
Range: 8 to 128 in steps of 8
Default: 8
This setting specifies the number of "Ind" points (single point status indications)
instantiated in the GGIO1 logical node. Changes to this setting take effect when the
Plus
D90
is restarted.
GGIO1 Indication 1, GGIO1 Indication 2,..., GGIO1 Indication 128
Range: any logic operand
Default: OFF
These settings assign logic operands to represent GGIO1 status indications.
The GGIO2 logical node provides access to the D90
virtual inputs are single-point control (binary) values that can be written by clients. They are
generally used as control inputs. GGIO2 provides access to protection virtual inputs
through the following IEC 61850 standard control model (ctlModel) services:
Status only
Direct control with normal security
SBO control with normal security
Settings are used to select the control model for each point. Enable each protection virtual
input used through GGIO2, and program the corresponding SPSCO ctlModel setting to the
appropriate control configuration.
Select the Settings > Communications > IEC 61850 > GGIO2 Control Configuration menu
to open the GGIO2 control configuration window.
IEC 61850 COMMUNICATIONS
Plus
protection virtual inputs. Protection
135