Advertisement

5.6 GROUPED ELEMENTS
XFMR HST PICKUP: Enter the hottest-spot temperature required for operation of the element. This setting should be
based on the maximum permissible hottest-spot temperature under emergency transformer loading conditions and
maximum ambient temperature.
XFMR HST DELAY: Enter an appropriate time delay before operation of the element.
e) AGING FACTOR

PATH: SETTINGS
GROUPED ELEMENTS
 AGING FACTOR
5
The Aging Factor element detects transformer aging in per-unit normal insulation aging. The element can be set for alarm
or trip whenever the computed aging factor is greater than the user-defined pickup setting for the specified time delay.
AGING FACTOR PICKUP: Enter a value above which the aging factor element will operate. The setting should be
greater than the maximum permissible aging factor under emergency loading conditions and maximum ambient tem-
perature.
5-208
Figure 5–102: TRANSFORMER HOTTEST-SPOT TEMPERATURE LOGIC
SETTING GROUP 1(6)
AGING FACTOR
FUNCTION: Disabled
AGING FACTOR PICKUP:
MESSAGE
2.0 pu
AGING FACTOR
MESSAGE
DELAY:
AGING FACTOR BLOCK:
MESSAGE
Off
AGING FACTOR TARGET:
MESSAGE
Self-Reset
Figure 5–103: AGING FACTOR LOGIC
T60 Transformer Protection System

TRANSFORMER
Range: Disabled, Enabled
Range: 1.1 to 10.0 pu in steps of 0.1
Range: 0 to 30000 min. in steps of 1
10 min.
Range: FlexLogic operand
Range: Self-reset, Latched, Disabled
5 SETTINGS
AGING FACTOR
GE Multilin