5.2 PRODUCT SETUP
Multiple LANS, No Redundancy
The following topology provides local configuration/monitoring through EnerVista software on LAN1, to which port 1 (P1) is
connected, access to the public network on LAN2, to which port 2 (P2) is connected and communications with SCADA on
LAN3, to which port 3 (P3) is connected. There is no redundancy.
5
d) NETWORK
As outlined in the previous section, when using more than one Ethernet port, configure each to belong to a different net-
work or subnet using the IP addresses and mask. Configure the network IP and subnet settings before configuring the rout-
ing settings.
PATH: SETTINGS
PRODUCT SETUP
 NETWORK PORT 1
 NETWORK PORT 2
5-30
Figure 5–6: MULTIPLE LANS, NO REDUNDANCY
EnerVista Software
LAN1
ML3000
P1
IP1/
MAC1

COMMUNICATIONS
PRT1 IP ADDRESS:
127.0.0.1
PRT1 SUBNET IP MASK:
MESSAGE
255.0.0.0
PRT1 GOOSE ENABLED:
MESSAGE
Enabled
PRT2 IP ADDRESS:
127.0.0.1
PRT2 SUBNET IP MASK:
MESSAGE
255.0.0.0
PRT2 REDUNDANCY:
MESSAGE
None
PRT2 PRP MCST ADDR:
MESSAGE
01-15-4E-00-01-00
PRT2 GOOSE ENABLED:
MESSAGE
Enabled
T60 Transformer Protection System
Public Network
SCADA
LAN2
ML3000
ML3000
P2
P3
IP2/
IP3/
MAC2
MAC3
UR

NETWORK 1(3)
Range: Standard IPV4 address format
Range: Standard IPV4 address format
Range: Enabled, Disabled
Range: Standard IPV4 address format
Range: Standard IPV4 address format
Range: None, Failover, PRP
None, Failover (if no PRP license)
Range: 01-15-4E-00-01-00 to 01-15-4E-00-01-FF
Range: Enabled, Disabled
5 SETTINGS
LAN3
859710A2.vsd