GE T60 Instruction Manual page 293

Transformer protection system ur series
Hide thumbs Also See for T60:
Table of Contents

Advertisement

5 SETTINGS
Table 5–17: T60 FLEXLOGIC OPERANDS (Sheet 7 of 9)
OPERAND TYPE
OPERAND SYNTAX
ELEMENT:
XFMR INST DIFF OP
Transformer
XFMR INST DIFF OP A
instantaneous
XFMR INST DIFF OP B
differential
XFMR INST DIFF OP C
ELEMENT:
XFMR HST-SPOT °C PKP
Hottest-spot
XFMR HST-SPOT °C OP
temperature
XFMR HST-SPOT °C DPO
ELEMENT:
XFMR LIFE LOST PKP
Transformer loss of
XFMR LIFE LOST OP
life
ELEMENT:
XFMR PCNT DIFF PKP A
Transformer percent
XFMR PCNT DIFF PKP B
differential
XFMR PCNT DIFF PKP C
XFMR PCNT DIFF 2ND A
XFMR PCNT DIFF 2ND B
XFMR PCNT DIFF 2ND C
XFMR PCNT DIFF 5TH A
XFMR PCNT DIFF 5TH B
XFMR PCNT DIFF 5TH C
XFMR PCNT DIFF OP
XFMR PCNT DIFF OP A
XFMR PCNT DIFF OP B
XFMR PCNT DIFF OP C
FIXED OPERANDS
Off
On
INPUTS/OUTPUTS:
Cont Ip 1
Contact inputs
Cont Ip 2
Cont Ip 1
Cont Ip 2
Cont Ip 96
Cont Ip 96
INPUTS/OUTPUTS:
Cont Op 1
Contact outputs,
Cont Op 2
current
(from detector on
form-A output only)
INPUTS/OUTPUTS:
Cont Op 1
Contact outputs,
Cont Op 2
voltage
(from detector on
Cont Op 1
form-A output only)
Cont Op 2
INPUTS/OUTPUTS
DIRECT INPUT 1 On
Direct inputs
DIRECT INPUT 32 On
INPUTS/OUTPUTS:
RemDPS Ip 1 BAD
Remote double-
RemDPS Ip 1 INTERM
point status inputs
RemDPS Ip 1 OFF
RemDPS Ip 1 ON
REMDPS Ip 2...
INPUTS/OUTPUTS:
REMOTE INPUT 1 On
Remote inputs
REMOTE INPUT 2 On
REMOTE INPUT 3 On
REMOTE INPUT 32 On
INPUTS/OUTPUTS:
Virt Ip 1
Virtual inputs
Virt Ip 2
Virt Ip 3
Virt Ip 64
GE Multilin
OPERAND DESCRIPTION
At least one phase of transformer instantaneous differential has operated
Phase A of transformer instantaneous differential has operated
Phase B of transformer instantaneous differential has operated
Phase C of transformer instantaneous differential has operated
The hottest-spot temperature element has picked up
The hottest-spot temperature element has operated
The hottest-spot temperature element has dropped out
The transformer loss of life element has picked up
The transformer loss of life element has operated
Transformer percent differential protection has picked up in phase A
Transformer percent differential protection has picked up in phase B
Transformer percent differential protection has picked up in phase C
The 2nd harmonic of transformer percent differential has blocked phase A
The 2nd harmonic of transformer percent differential has blocked phase B
The 2nd harmonic of transformer percent differential has blocked phase C
The 5th harmonic of transformer percent differential has blocked phase A
The 5th harmonic of transformer percent differential has blocked phase B
The 5th harmonic of transformer percent differential has blocked phase C
At least one phase of transformer percent differential has operated
Phase A of transformer percent differential has operated
Phase B of transformer percent differential has operated
Phase C of transformer percent differential has operated
Logic = 0. Does nothing and may be used as a delimiter in an equation list;
used as 'Disable' by other features.
Logic = 1. Can be used as a test setting.
On
(will not appear unless ordered)
On
(will not appear unless ordered)
Off
(will not appear unless ordered)
Off
(will not appear unless ordered)
On
(will not appear unless ordered)
Off
(will not appear unless ordered)
IOn
(will not appear unless ordered)
IOn
(will not appear unless ordered)
VOn
(will not appear unless ordered)
VOn
(will not appear unless ordered)
VOff
(will not appear unless ordered)
VOff
(will not appear unless ordered)
Flag is set, logic=1
Flag is set, logic=1
Asserted while the remote double-point status input is in the bad state
Asserted while the remote double-point status input is in the intermediate
state
Asserted while the remote double-point status input is off
Asserted while the remote double-point status input is on
Same set of operands as per REMDPS 1 above
Flag is set, logic=1
Flag is set, logic=1
Flag is set, logic=1
Flag is set, logic=1
On
Flag is set, logic=1
On
Flag is set, logic=1
On
Flag is set, logic=1
On
Flag is set, logic=1
T60 Transformer Protection System
5.5 FLEXLOGIC
5
5-157