...4.3.5 Set Up Control Page (default control actions)
dFA-PV
dEF-OP
HOLd
NONE
dEF-OP
----
rSP–x
not enabled –
Input Assignment
Page
rSP–x
enabled
dFA-SP
dEF-OP
LOCAL
NONE
dEF-SP
----
SELECt
------
C-tYPE
bNdLSS
Ht-CL
Std
C-tYPE
P-PrOP
dFA-Fb
HOLd
NONE
Default Action (Process Variable)
Select the default control action required if the process variable exceeds its fault detection level
(set in the
page,
Set Up Input
dEF–OP
revert to manual control mode and change the control output to the
Default Output
HOLd
revert to manual control mode and hold the output at its current value.
NONE
no action.
Default Output
Set the default control output value used if the process variable exceeds the fault detection level
(between 0 and 100% in 1 % increments).
Note. For boundless motorized valve control, the default output setting can only be 0
100%.
Default Action (Set Point)
Select the default control action required if the remote set point exceeds its fault detection level
(set in the
Set Up Input Page
dEF–SP
revert to local set point and use the
LOCAL
revert to local set point.
NONE
no action.
Default Set Point
Set the default control set point value used if the remote set point exceeds the fault detection
level (in engineering units).
Default Action (Position Feedback)
Select the default control action required if the position feedback exceeds its fault detection level
(set in the
Set Up Input Page
HOLd
revert to manual control mode and hold the valve at its current position.
NONE
no action.
Return to
Select Controller
4 CONTROL CONFIGURATION LEVEL...
BASIC CONFIGURATION LEVEL
value (see next frame).
,
BASIC CONFIGURATION LEVEL
,
BASIC CONFIGURATION LEVEL
frame.
):
):
value (see next frame).
Default Set Point
):
or
43