...3 BASIC CONFIGURATION LEVEL
3.7 Set Up Analog Output
Information.
• Fitted analog outputs – assignable to retransmit any input (process variable, remote set point or position feedback) or
provide the control output.
• Selectable retransmission range – allows maximum resolution on range of interest.
• Adjustable output range – for non-standard and reversed outputs.
Note. The example below shows analog output 1 set to retransmit part of process variable 1's engineering range (250
to 750°C) as a 4.0 to 20.0mA current output.
Select Analog
Output
PV1 — Process Variable, Controller 1
SP–1 — Control Set Point, Controller 1
PFB–1 — Position Feedback, Controller 1
PV2 — Process Variable, Controller 2
Position 1
SP–2 — Control Set Point, Controller 2
PFB–2 — Position Feedback, Controller 2
PV3 — Process Variable, Controller 3
PV4 — Process Variable, Controller 4
Oh–1 — Control Output (heat), Controller 1
Oc–1 — Control Output (cool), , Controller 1
Position 6
Oh–2 — Control Output (heat), Controller 2
Oc–2 — Control Output (cool), Controller 2
OP–1 — Control Output, Controller 1
OP–2 — Control Output, Controller 2
20
Select Output Source
Setting Output Ranges
1000°C (Engineering Range High)
750°C (Retransmission Range High)
Range to be
transmitted
250°C (Retransmission Range Low)
0°C (Engineering Range Low)
20.0mA (Output Range High)
4.0mA (Output Range Low)