...4 CONTROL CONFIGURATION LEVEL
4.3 Set Up Control
Information.
• Control types – Current Proportioning, Time Proportioning (and On/Off), Position-proportioning (motorized valve control
with feedback), Boundless and Heat/Cool.
• Programmable power-up control modes and outputs.
• Reverse and direct control actions.
• High and low output limits.
• Programmable fault actions – enable fault actions on any of the inputs (process variable, remote set point and position
feedback) to be controlled.
4.3.1 Set Up Control Page (control type)
SEt UP
ContrL
SELECt
CtrL 2
CtrL 1
NONE
C-tYPE
bNdLSS
P-PrOP
Ht-CL
Std
PFMOdE
------
Process
Variable
Set Point
36
Page Header – Set Up Control.
Select Controller
Select the controller to be programmed (1 or 2).
Note. In the remaining frames press the
Control Type
Select the control type required:
bNdLSS
–
(Boundless) for motorized valve control, without position feedback
P-PrOP
–
(Position-Proportioning) motorized valve control, with position feedback
Ht-C
L
–
(Heat/Cool) dual output control
Std
–
(Standard) current proportioning, time proportioning and on/off
Continued on page 38.
Time Proportioning
P.I.D.
Control
Terms
Analog Output
On/Off
Control
C1900 Controller
Fig. 4.5 Standard Control Schematic Diagram
switch to view the controller selected.
Feedback
Relay or
Digital
Outpuu
4 to 20mA
Relay or
Digital
Outpuu
Process